PowerFlex 700 with Vector Control Option Custom Firmware 5

Rockwell Automation Publication 20B-IN020C-EN-P - January 2014

Custom Firmware Parameters

Advanced Parameter View must be selected (parameter 196 [Param Access Lvl] set to 1,
“Advanced”).

Parameters 692 through 699 provide various metering points for the function. Refer to pages

8

and

9

for descriptions.

Custom Firmware Parameters

Fi

le

Gr

oup

No

.

Parameter Name and Description

See User Manual for symbol descriptions

Values

Re

lated

APPLIC

AT

IONS

O

il W

ell Pump

680 [Pump Cycle Store]

Used to store the torque waveform over the course of a
pump cycle. This is used to determine the downstoke when
in “Automatic” or “Position” mode.

With the drive running at the desired speed, change [Pump
Cycle Store] to “Enabled” and press enter. Over the next few
cycles the waveform is stored and [Pump Cycle Store]
changes back to “Disabled”.

If after 5 pump cycles [Pump Cycle Store] has not changed
back to “Disabled”, waveform variations can be excessive.

Default:

Options:

0

0
1

“Disabled”

“Disabled”
“Enabled”

681 [Set Top of Strok]

Stores the top of pump stroke cycle.

With the drive running at the desired speed, change [Set Top
of Strok] to “Enabled” and press enter when the rod is at the
highest position. [Set Top of Strok] automatically changes
back to “Disabled”.

Default:

Options:

0

0
1

“Disabled”

“Disabled”
“Enabled”

682 [Pump Off Control]

Used to enable Pump Off control.

Default:

Options:

0

0
1
2

“Disabled”

“Disabled”
“Baseline Set”
“Fixed Setpt”

“Disabled” (0) - Pump Off control is not active.

“Baseline Set” (1) - The control uses a torque baseline created after any start of the drive (first ten cycles).
IMPORTANT: It is critical that this data is gathered from a full well.

“Fixed Setpt” (2) - The control uses the value in [Torque Setpoint]. Use the value in [% Drop Torque] as a
guideline in “Automatic” or “Position” mode. In “Cycle” mode use [% Cycle Torque] as a guideline.