PowerFlex® DC Drive - Frame C Armature Circuit Fuse Replacement
3
3. Loosen, but do not remove, the screws that secure the top cover to the
drive, then slide the cover up and off the drive chassis.
Important: The HIM assembly is connected via a cable to the Control
board and therefore will not pull free from the drive until
disconnected. See step 4 below for instructions.
Important: Mark all connections and wires before removal to avoid
incorrect wiring during reassembly.
4. Disconnect the HIM Communication cable from the connector on the
upper right corner of the Control board and set the cover aside.
STS
PORT
MOD
NET A
NET B
FU1
FV1
U
V
C
D
W
Tightening torque:
1.5 N-m (13.3 lb.-in.)
Pull tabs out
to disconnect
cable.