Warning – Rockwell Automation 140U Q and M-Frame Circuit Breakers Installation of Q-Frame Circuit Breakers User Manual

Page 5

Advertising
background image

PUSH-TO-TRIP

I

1

Magnetic

Trip

Unit

Magnetic

-

Amps

Cat.

Multiples of In.

No.

Page 5

Fig. 4-2

Unit Magnetic Adjustment Buttons

WARNING

CONTACT WITH ENERGIZED EQUIPMENT CAN
RESULT IN DEATH, SEVERE PERSONAL INJURY,

OR

SUBSTANTIAL PROPERTY DAMAGE. DO NOT

NANCE ON EQUIPMENT WHILE IT

IS ENERGIZED.

ALWAYS VERIFY THAT NO VOLTAGE

IS PRESENT

BEFORE PROCEEDING WITH THE TASK, AND

ALWAYS FOLLOW GENERALLY ACCEPTED SAFETY

PROCEDURES.

ATTEMPT TO INSTALL

OR PERFORM MAINTE-

Note: When replacing an existing circuit breaker of

the types listed above, make sure the voltage,
continuous current, and interrupting rating of the

new circuit breaker are suitable.

4.

MANUAL OPERATION, AND
MAGNETIC TRIP UNIT ADJUSTMENT

Manual Operation

Manual operation of the circuit breaker is controlled by

the circuit breaker handle and the PUSH-TO-TRIP button

in the trip unit. The circuit breaker handle has three posi-

tions, two of which are shown on the cover with raised let-
tering to indicate

ON and OFF. On the handle, ON, OFF,

and trip are also shown by a color-coded strip for each
circuit breaker handle position: red for

ON, white for

tripped, and green for OFF (see Fig. 4-1).

Circuit Breaker Reset

After a trip operation, the circuit breaker is reset by mov-

ing the circuit breaker handle to the Reset (extreme

OFF)

position.

Note:

In the event of a thermal (overload) trip the

circuit breaker cannot be reset immediately.

In a

breaker with a thermal-magnetic type trip

unit the

thermal element needs to cool

(up to approximately

five minutes) before it can be reset. A circuit breaker
with a electronic RMS trip

unit simulates the thermal

element with an electronic “thermal memory” that
also requires

up to five minutes to “cool” before it

can be re-energized.

No circuit breaker should be

until the cause

of trip

is known and the situation rectified.

PUSH-TO-TRIP Button

The PUSH-TO-TRIP button operates the circuit breaker
tripping function and may be used to periodically exercise
the operating mechanism. In thermal-magnetic trip units,
the button is designed to be operated by a small screw-
driver. The rating plug in electronic RMS trip units con-
tains the PUSH-TO-TRIP button which is operated by
finger pressure. There is no PUSH-TO-TRIP button in the

molded case switch.

Thermal-Magnetic Trip Unit Adjustment

The magnetic element of each pole of the trip unit can be
adjusted by rotating the adjustment buttons on the front
face of the trip unit with a screwdriver. The buttons have
several settings as indicated on the nameplate with

40752-078(1)

Effective

5/02

Advertising