Rockwell Automation 140U K-Frame CB Alarm Switch and Alarm /Auxiliary Switch Combination User Manual

Page 7

Advertising
background image

Fig.

Cover Screw

tion Positions

Modification

Label

Terminal Black

I

Terminal Block
Connection

Diaaram
(When Used)

Pigtail Lead

C o n n e c t i o n

Diagram
Label
(When Used)

Fig.

I I. Preferred Mounting Locations for Accessory

Nameplate Labels

Pigtail Leads

ASL Switch

Blue

Auxiliary Switch

Red

M a k e

T

(Alarm)

Leads Are Bundled and
T a g g e d “ B ”

Terminal Block

Blue

L

o

Red

ASL Switch

a

Leads Are Bundled and

Tagged “A”

Red

b

B l u e

Auxiliary Switch

Fig.

12. Alarm

Switch

Auxiliary

Switch Connection Diagram

b.

Circuit breaker handle ON

Check that make

contact(s) are open and break contact(s) are
closed.

C .

Press PUSH-TO-TRIP button

Check that

make contact(s) are closed and break con-

tact(s) are open.

d.

If ASL switch fails test, make sure that module
is properly seated in trip unit slots. If problem
persists. contact Allen-Bradley.

2-17. Test auxiliary switch (when supplied). Connect con-

tinuity tester or ohmmeter across pigtail leads or
terminal block connections. Check continuity as fol-

lows:

a.

Circuit breaker handle OFF
“a” contact open
“b” contact closed.

b.

Circuit breaker handle ON
“a” contact closed
“b” contact open.

40752-035(1)

Effective 3/02

Page 7