Rockwell Automation 150-SM3_SM4 SMC-50 Soft Starter I/O Option Module Installation User Manual

Page 3

Advertising
background image

PN-164120
DIR 10000152878 (Version 01)
Publication 150-IN052B-EN-E

Specification

Type of Output

Electromagnetic Relay Contact

Number of Contacts

1

Type of Contact

Programmable: Normally Open (N.O.) or
Normally Closed (N.C.)

Rated Operational Current (Inductive)

3A @ 120V AC, 1.5A @ 240V AC

Rated Operational Current (Resistive)

8A @ 250V AC, 5A @ 30V DC

Rated Thermal Current (Ith)

5A (AC)

Max. Make / Break

3600VA Make, 360VA Break

UL Utilization Ratings

AC-15, B300 (AC Pilot Duty: NEMA)

Output Delay Time (max)

On-to-Off: 25 mS; Off-to-On 30 mS

Relay Life (electrical-Inductive Load
cos ø = 0.4)

250,000 operations
(3A @ 120V AC, 1.5A @ 240V AC)

Relay Life (mechanical)

10 million operations

150-SM4 Input and Output Specifications

Field Wiring Terminal Identification

A9

In

COM

NC

120 / 240V AC

NOTE: For control wiring
details refer to the SMC-50
User Manual

Inputs

InA1 InA2 InA3 InA4

AuxA1

AuxA2

AuxA3

Relay Outputs

A11 A12

L1

A1

A2

A3

A4

A5

A6

A7

A8

L1

L1

L1

L2

L2

L2

L2

A10

UL/CSA/NEMA

IEC

Nominal Operating Voltage
Operating Voltage Range

120/240V AC
85 to 264V AC @ 47 to 63 Hz
9.7 mA @ 47 Hz, 9.7 mA @ 62.4 Hz

On-state Current, Minimum

On-state Voltage, Minimum

Off-state Current, Maximum

Off-state Voltage, Maximum

74.5V AC @ 47 Hz, 55.9V AC @ 62.4 Hz
68.8V AC @ 47 Hz, 53.6V AC @ 62.4 Hz
9.0 mA @ 47 Hz, 9.3 mA @ 62.4 Hz

3.64 A
On-to-Off: 30 mS, Off-to-On: 25 mS

Inrush Current Max
Input Delay Time
Rated Insulation Voltage
Rated Impulse Voltage
Dielectric Withstand

Control Circuit:

150-SM4

Optional Inputs:

Terminals A1 and A2

NA 240V
NA

3000V

1600V AC

2000V

UL/CSA/NEMA

IEC

Nominal Operating Voltage
Operating Voltage Range

120/240V AC
85 to 264V AC @ 47 to 63 Hz
5.1 mA @ 47 Hz, 5.0 mA @ 62.4 Hz

On-state Current, Minimum

On-state Voltage, Minimum

Off-state Current, Maximum

Off-state Voltage, Maximum

74.5V AC @ 47 Hz, 55.8V AC @ 62.4 Hz
68.6V AC @ 47 Hz, 53.5V AC @ 62.4 Hz
4.7 mA @ 47 Hz, 4.8 mA @ 62.4 Hz

3.64 A
On-to-Off: 30 mS, Off-to-On: 25 mS

Inrush Current Max
Input Delay Time (Maximum)
Rated Insulation Voltage
Rated Impulse Voltage
Dielectric Withstand

Control Circuit:

150-SM4

Optional Inputs:

Terminals A3 and A4

(1)

Control Circuit:

150-SM4

Optional Outputs:

Terminals A6 thru A11

NA 240V
NA

3000V

1600V AC

2000V

(1) Meets IEC Type 2 specification per IEC 60947-1 for 240V AC only

NOTE: For additional information refer to the SMC-50 User manual (150-UM011x-EN-P) available from www.ab.com - Publications Library - Literature Library