Where local codes and standards permit and UL listing

is not required, internal accessories can be field

installed in sealed circuit breakers. In this case, UL list
i

ng becomes invalid and the label should be removed.

File E7819.

Before attempting to install the ASL switch or acces-

sory combination, check that the catalog number is

correct as ordered and that the rating of the acces-

sory(s) satisfies the job requirements.

Depending on the model ordered, connections for the
ASL switch and auxiliary switch contacts are in one of
four forms. The standard wiring configuration is pigtail
leads exiting the rear of the base directly behind the
accessory. Optional configurations include a terminal
block mounted on the same side of the base as the
accessory, leads exiting the side of the base where the
accessory is mounted, and leads exiting the rear of the
base on the side opposite the accessory. The 18-inch
long pigtail leads are color coded for identification; iden-
tification labels are provided for pigtail leads and termi-
nal block points. For allowable locations of all acces-
sories, refer to

Selection Guide.

No more than three pigtail leads can be routed
through the rear trough in the circuit breaker base.

This instruction leaflet (IL) gives detailed procedures for
installing the ASL switch and ASL switch/auxiliary switch
combination (accessory combination).

Table 1-1. Alarm (Signal)/Lockout and Auxiliary Switch

Electrical Rating Data

①➁➂

Maximum

Freq

Maximum

Dielectric

Voltage

Current

Withstand

(V)

(A)

Voltage (V)

600

50/60 Hz

6

2500

125

DC

0.5

250

DC

0.25

① Endurance- 400 electrical operations plus 5600

mechanical operations

➁ Pigtail wire size - No. 18 AWG (0.82 mm)

➂ Terminal block is listed for use with one or two No. 18 to

No. 14 AWG solid or stranded copper wires. Torque is
7 Ib-in (0.8 N.m)

➃ Non-inductive load

2. INSTALLATION

The ASL switch(es) and accessory combination can be
field-installed in N

-Frame circuit breakers.

Page 2

NOTICE

NOTICE

Fig. 2-1. Alarm (Signal) Lockout Switch Kit

40752-094 (1)

Effective 04/02

The ASL switch (shown in kit form in Fig. 2-1) and accessory

sory combination, is installed in the right or left accessory
mounting cavity of a 2-, 3-, or 4-pole circuit breaker. An

before the circuit breaker is mounted in an electrical sys-

tem. To install the auxiliary switch, perform the following

procedures:

auxiliary switch must be installed in the circuit breaker

Plug-in Module with

Pigtail Leads (single

ASL Switch Shown)

Accessory
Identification
Label

Connection
Diagram Label
(Pigtail Lead
Label Shown)

Advertising