1397 NEMA Type 1 Dynamic Brake

3

1397-5.14 March, 1997

1

Remove and lockout all incoming power to the drive. Remove
the (8) cover screws to remove the brake cover.

Installation

(continued)

SIDE

194.4mm

(7.65 In.)

TOP

DANGER

810293-200A

DISCONNECT INPUT POWER
BEFORE SERVICING EQUIPMENT.
FAILURE TO OBSERVE THESE
PRECAUTIONS COULD RESULT
IN SEVERE BOCILY INJURY OR
LOSS OF LIFE.

!

DANGER

COUPER L'ALIMENTATION AVANT
LA MAINTENANCE. SI CES
PRECAUTIONS NE SONT PAS
PRISES, ON RISQUE DES
BLESSURES GRAVES OU MORTELLES.

!

`

DGI

FRONT

246.0mm

(9.69 In.)

755.3mm

(29.74 In.)

246.0mm

(9.69 In.)

755.3mm

(29.74 In.)

A1

S2

A1

45

A2
S1

1 2 3 4 5 6

GRD

REPLACE FUSES
WITH

16FU 17FU
LITTLEFUSE
type KLDR
600V .6A

COVER REMOVED

27.94mm (1.1 IN.) DIA. CONDUIT HOLES
— (2) PLACES —

88.9mm

×

88.9mm

(3.5 IN.

×

3.5 IN.)

REMOVABLE
CONDUIT PLATE

Cover

Screw

Cover

Screw

Cover

Screw

Cover

Screw

Cover

Screw

Cover

Screw

Cover

Screw

Cover

Screw

2

Included with the Dynamic Brake kit is a 1.22m (48 In.)
interconnection cable to supply AC power between the drive’s
fuses and the Dynamic Brakes’ control transformer. The
Dynamic Brake is mounted using (4) user supplied mounting
fasteners (6mm fasteners is recommended). Leave a minimum
of 0.20 In. (5mm) space between the head of the screw and the
mounting panel to slide the brake assembly over the heads of the
fasteners.

Advertising