Grounding, Drive – Rockwell Automation 1329L AC Induction Motors User Manual User Manual

Page 9

Advertising
background image

AC Induction Motors

9

Procedure:

1. Connect for low or high voltage as shown.

2. Check that the direction of air flow is in agreement with the

“direction of air flow” arrows mounted on the motor. If
directional flow is incorrect, interchange power leads to T1 & T2
or U1 & V1.

Grounding

The user is responsible for assuring that the grounding method is in
accordance with the National Electric Code and the applicable local
codes. The ground connection should be a solid and permanent
metallic connection between the ground point, the motor terminal
housing and the motor frame. A ground lead is provided inside the
terminal box.

Due to the need to carry higher frequency ground currents (from
switch voltage waveforms) the ground connection/path must be low
impedance/low resistance. Such ground currents exist during normal
operation on inverter power.

Drive

L180-L320 frame motors are supplied with a shaft suitable for a belt
or coupled drive.

Belt loads should be checked against maximum allowable radial loads
under

“Shaft Loads - Axial and Radial” on page 13

. Contact Allen-

Bradley to determine L440 frame belt load requirements.

Frames L360S and L400S are suitable for coupled duty only, larger
shafts are supplied for belted duty.

(Delta)

(Star)

T6

T4

T5

T6

T4

T5

T1

T2

T3

L1

L2

L3

T1

T2

T3

L1

L2

L3

Low Volts

Line

High Volts

(Delta)

(Star)

W2

U1 = Black
U2 = Green

V1 = Blue
V2 = White

W1 = Brown
W2 = Yellow

U2

V2

W2

U2

V2

U1

V1

W1

L1

L2

L3

U1

V1

W1

L1

L2

L3

Low Volts

Line

High Volts

or

or Connection Diagram shown on

page 7

.

!

ATTENTION: Connect an appropriate equipment
grounding conductor to the drive ground terminal, motor
frame, transformer enclosure (if used), drive electrical
enclosure and an appropriate grounding electrode. Failure
to observe these precautions could result in personal injury
and/or death.