Parallel use for redundancy, Daisy chaining of outputs, Inductive and capacitive loads – Rockwell Automation 1606-XLP60EQ Power Supply Reference Manual User Manual

Page 20

Advertising
background image

All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

20

Rockwell Automation Publication 1606-RM007A-EN-P - February 2014

Bulletin 1606 Switched Mode Power Supplies

22.6. Parallel Use for Redundancy

Power supplies can be paralleled for redundancy to gain higher system
availability. Redundant systems require a certain amount of extra power
to support the load in case one power supply unit fails. The simplest way is
to put two power supplies in parallel. This is called a 1+1 redundancy. In
case one power supply unit fails, the other one is automatically able to
support the load current without any interruption. Redundant systems for
a higher power demand are usually built in a N+1 method. E.g. five power
supplies, each rated for 2.5A are paralleled to build a 10A redundant
system.

Please note: This simple way to build a redundant system does not cover
failures such as an internal short circuit in the secondary side of the power
supply. In such a case, the defect unit becomes a load for the other power supplies and the output voltage can not be
maintained any more. This can only be avoided by using decoupling diodes which are included in the redundancy
module 1606-XLPRED.

XLPRED

IN 1

+

-

+

-

L
N

I

I

XLP60EQ

L N

Output

Input

+ +

- -

XLP60EQ

L N

Output

Input

+ +

- -

Output

Load

+

- -

+

-

IN 2

Voltage
Monitor

Recommendations for building redundant power systems:

a)

Use separate input fuses for each

power supply.

b)

Use separate mains systems for each power supply whenever possible.

c)

Monitor the individual power supply units.

d)

1+1 Redundancy is allowed up to an ambient temperature of 60°C.
N+1 Redundancy is allowed up to an ambient temperature of 45°C.

e)

It is desirable to set the output voltages of all units to the same value (± 100mV) or leave it at the factory setting.

22.7. Daisy Chaining of Outputs

Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current
through one terminal pin does not exceed 25A. If the current is higher, use a separate distribution terminal block.

Fig. 22-3 Daisy chaining of outputs

Fig. 22-4 Using distribution terminals

Power

Supply

+ +

- -

Input

Output

Load

+

-

max 25A!

Power

Supply

+ +

- -

Input

Output

Load

+

-

Distribution

Terminals

Power

Supply

+ +

- -

Input

Output

Power

Supply

+ +

- -

Input

Output

22.8. Inductive and Capacitive Loads

The unit is designed to supply any type of load, including unlimited capacitive and inductive loads.

Advertising