Ac-input – Rockwell Automation 1606-XLP60EQ Power Supply Reference Manual User Manual

Page 4

Advertising
background image

All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

4

Rockwell Automation Publication 1606-RM007A-EN-P - February 2014

Bulletin 1606 Switched Mode Power Supplies

3. AC-Input

AC input

nom.

AC 100-240V

-15% / +10%, TN/TT/IT-mains

AC input range

85-264Vac

continuous operation, reduce output power linearly
to 50W between 90Vac and 85Vac at ambient
temperatures above +45°C, see Fig. 3-5

264–300Vac

<

0.5s

Allowed voltage L or N to earth

max.

264Vac or 375Vdc

Input frequency

nom.

50–60Hz

±6%

Turn-on voltage

typ.

65Vac

Shut-down voltage

typ.

see Fig. 3-1

AC 100V

AC 120V

AC 230V

Input current (rms)

typ.

1.14A

0.98A

0.58A

at 24V, 2.5A see Fig. 3-3

Power factor *)

typ.

0.61

0.58

0.50

at 24V, 2.5A see Fig. 3-4

Crest factor **)

typ.

3.2

3.3

3.7

at 24V, 2.5A

Start-up delay

typ.

170ms ***)

110ms ***)

90ms

see Fig. 3-2

Rise time

typ.

50ms

50ms

60ms

at 24V, 2.5A, 0mF, see Fig. 3-2

120ms

110ms

140ms

at

24V,

2.5A,

2.5mF

Turn-on

overshoot

max.

200mV 200mV 200mV

see

Fig.

3-2

*)

The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.

**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
***) At low temperatures, start-up attempts may occur which extends the start-up delay.

Fig. 3-1

Input voltage range

Fig. 3-2

Turn-on behavior, definitions

85

Rated

input range

max.

500ms

V

IN

V

OUT

300Vac

264

65

Start-up

delay

Rise

Time

Overshoot

- 5%

Output
Voltage

Input
Voltage

Fig. 3-3

Input current vs. output load at 24V

Fig. 3-4

Power factor vs. output load at 24V

2.5A

0.5

1.5

0

0

0.4

1.2A

Input Current, typ.

2.0

0.8

1.0

1.0

0.6

0.2

b

c

a

a) 100Vac
b) 120Vac
c) 230Vac

Output Current

2.5A

0

0.5

1.0

2.0

0.40

0.45

0.50

0.55

0.60

0.65

Power Factor, typ.

a) 100Vac
b) 120Vac
c) 230Vac

b

c

a

1.5

Output Current

Advertising