Functional diagram, Terminals and wiring – Rockwell Automation 1606-XLS240F, -XLS240F-D Power Supply Reference Manual User Manual

Page 12

Advertising
background image

All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

12

Rockwell Automation Publication 1606-RM045A-EN-P — March 2014

Bulletin 1606 Switched Mode Power Supplies

11. Functional Diagram

Fig. 11-1 Functional diagram

+

+

-
-

DC-ok
contact

Output

Over-

Voltage

Protection

PFC

Converter

Output

Voltage

Regulator

Power

Converter

Output

Filter

DC-ok
Relay

Output

Voltage

Monitor

Output

Power

Manager

Temper-

ature

Shut-

down

Overload

LED
DC-ok

LED

Input Fuse
Input Filter
Input Rectifier
Active Transient Filter &
Inrush Current Limiter

V

OUT

L

N

12. Terminals and Wiring

Bi-stable, quick-connect spring clamp terminals. IP20 Finger safe construction. Suitable for field- and factory
installation. Shipped in open position.

Input Output

DC-OK-Signal

Type

spring-clamp terminals

spring-clamp terminals

spring-clamp terminals

Solid wire

0.5-6mm

2

0.5-6mm

2

0.5-6mm

2

Stranded wire

0.5-4mm

2

0.5-4mm

2

0.5-4mm

2

American Wire Gauge

20-10 AWG

20-10 AWG

20-10 AWG

Wire stripping length

10mm / 0.4inch

10mm / 0.4inch

10mm / 0.4inch

Screwdriver not

applicable

not

applicable

not

applicable

Recommended tightening torque

not applicable

not applicable

not applicable

Pull-out force

10AWG:80N, 12AWG:60N, 14AWG:50N, 16AWG:40N (according to UL486E)

Fig. 12-1 Connecting a wire

Instructions:
a) Use appropriate copper cables that are designed for minimum

operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C minimum
90°C for ambient up to 70°C minimum.

b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal

connection!

d) Up to two stranded wires with the same cross section are

permitted in one connection point (except PE wire).

e) Do not use the unit without PE connection.
f) Unused terminal compartments should be securely tightened.
g) Ferrules are allowed.

1. Insert the wire

2. Close the lever

To disconnect wire:

reverse the above procedure.