Front side and user elements – Rockwell Automation 1606-XLS240F, -XLS240F-D Power Supply Reference Manual User Manual

Page 13

Advertising
background image

All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM045A-EN-P — March 2014

13

Bulletin 1606 Switched Mode Power Supplies

13. Front Side and User Elements

Fig. 13-1 Front side

A Input

Terminals (Quick-connect spring-clamp terminals)

N,

L

Line input

PE

(Protective

Earth)

input


B Output

Terminals (Quick-connect spring-clamp terminals, two pins per

pole)
+ Positive output

– Negative (return) output


C DC-OK

Relay

Contact

(Quick-connect spring-clamp terminals)

The DC-OK relay contact is synchronized with the DC-OK LED.
See section 8 for details.


D Output voltage potentiometer

Multi turn potentiometer;
Open the flap to adjust the output voltage. Factory set: 48.0V


E DC-OK

LED

(green)

On, when the output voltage is >90% of the adjusted output voltage


F Overload

LED

(red)

On, when the voltage on the output terminals is <90% of the adjusted
output voltage, or in case of a short circuit in the output.
Input voltage is required
Flashing, when the unit has switched off due to over-temperature.

Indicators, LEDs

Overload LED

DC-OK LED

DC-OK Contact

Normal mode

OFF

ON

Closed

During BonusPower

OFF

ON

Closed

Overload (V

OUT

< 90%)

ON

OFF

Open

Output short circuit

ON

OFF

Open

Temperature Shut-down

Intermitted

OFF

Open

No input power

OFF

OFF

Open