Rockwell Automation 1606-XLE96B-2_XLE120E-2_XLE240E-3_XLE240F-3 DC--Power Supply User Manual

Page 3

Advertising
background image

XLE96B-2, XLE120E-2, XLE-240E-3, XLE240F-3: Power Supply Instruction Manual
XLE96B-2, XLE120E-2, XLE-240E-3,
XLE240F-3: Bedienungsanleitung für Stromversorgung

Technical Data

1)

Technische

Daten

1)

1606-XLE96B-2

1606-XLE120E-2

1606-XLE240E-3

1606-XLE240F-3

Output Voltage

Ausgangsspannung

nom. DC 12-15V

DC 24-28V

DC 24-28V

DC 48-56V

Factory Setting

6)

Werkseinstellung

6)

“Single-Use”,

typ. 12.0V 24.1V 24.1V 48.0V

Output Current

Ausgangsstrom

nom. 8A (12V), 6.4A (15V)

5A (24V), 4.3A (28V)

10A (24V), 8.6A (28V)

5A (48V), 4.3A (56V)

PowerBoost

2)

-

6A (24V), 5.2A (28V)

12A (24V), 10.3A (28V) 6A (48V), 5.2A (56V)

Output Power

Ausgangsleistung

nom. 96W 120W 240W 240W

PowerBoost

2)

-

144W 288W 288W

Output Ripple & Noise Voltage

3)

Ausgangswelligkeit

3)

max. 100mVpp

50mVpp 50mVpp 100mVpp

AC Input Voltage

AC Eingangsspannung

nom. 2AC 380-480V

-15/+20%

2AC

380-480V

-15/+20%

3AC

380-480V

-15/+20%

3AC

380-480V

-15/+20%

Input Frequency

Eingangsfrequenz

nom. 50-60Hz

±6%

50-60Hz

±6%

50-60Hz

±6%

50-60Hz ±6%

AC Input Current

7)

AC

Eingangsstrom

7)

400 / 480Vac, typ. 0.64A / 0.56A

0.75A / 0.68A

0.7/0.6A / Phase

0.7/0.6A / Phase

Power Factor

6)

Leistungsfaktor

6)

400 / 480Vac, typ. 0.44 / 0.42

0.45 / 0.43

0.53 / 0.52

0.53 / 0.52

Allowed Voltage Phase to Earth

Erlaubte Spannung Phase zu Erde

IEC

60664-1 <500Vac <500Vac <500Vac <500Vac

EN 61000-3-2

EN 61000-3-2

PFC-Norm Yes / Ja

Yes / Ja

Yes / Ja

Yes / Ja

Input Inrush Current

4)

Einschaltspitzenstrom

4)

typ. 4A peak, 0.5A

2

s

4A peak, 0.5A

2

s

4A peak, 0.5A

2

s

4A peak, 0.5A

2

s

DC Input Voltage

5)

DC

Eingangsspannung

5)

nom. 600Vdc

-25/+30%

600Vdc

-25/+30%

600Vdc

-25/+30%

600Vdc

-25/+30%

Hold-up Time

6)

Pufferzeit

6)

400 / 480Vac, typ. 33ms / 58ms

27ms / 48ms

34 / 54ms

34 / 54ms

Efficiency

6)

Wirkungsgrad

6)

400 / 480Vac, typ. 86.7% / 86.4%

90.4% / 90.0%

92.8 / 92.9%

92.8 / 92.9%

Power Losses

6)

Verlustleistung

6)

400 / 480Vac, typ. 14.7W / 15.1W

12.7W / 13.3W

18.6 / 18.6W

18.6 / 18.6W

Operational Temperature Range Betriebstemperaturbereich

nom. -25°C - +70°C

-25°C - +70°C

-25°C - +70°C

-25°C - +70°C

Output Derating

Leistungsrücknahme

60°C … 70°C 2.5W/°C

3W/°C

6W/°C

6W/°C

Storage Temperature Range

Lagertemperaturbereich

nom. -40°C - +85°C

-40°C - +85°C

-40°C - +85°C

-40°C - +85°C

Humidity

8)

Feuchte

8)

,

IEC 60068-2-30 5 - 95% r.H.

5 - 95% r.H.

5 - 95% r.H.

5 - 95% r.H.

Vibration Schwingen

IEC

60068-2-6 2g 2g 2g 2g

Shock Schocken IEC 60068-2-27 30g 6ms, 20g 11ms

30g 6ms, 20g 11ms

30g 6ms, 20g 11ms

30g 6ms, 20g 11ms

Degree of Pollution (not conductive) Verschmutzungsgrad

(nicht leitend)

EN

50178

/

62103 2 2 2 2

Degree of Protection

Schutzart

EN

60529 IP20 IP20 IP20 IP20

Class of Protection

Schutzklasse

IEC 61140 I

9)

I

9)

I

9)

I

9)

Over-temperature Protection

10)

Übertemperaturschutz

10)

OTP Yes / Ja

Yes / Ja

Yes / Ja

Yes / Ja

Output Over-voltage Protection

10)

Überspannungsschutz

Ausgang

10)

OVP,

max. 20Vdc 32Vdc 32Vdc 60Vdc

Touch (Leakage) Current

11)

PE-

Ableitstrom

11)

max. 0.18mA / 0.25mA

0.18mA / 0.25mA

0.22mA / 0.31mA

0.22mA / 0.31mA

Return Voltages Resistance

12)

Rückspeisefestigkeit

12)

max. 25Vdc 35Vdc 35Vdc 63Vdc

Parallel Use

Parallelschaltbar

Yes / Ja

13)

Yes / Ja

13)

Yes / Ja

14)

Yes / Ja

14)

Serial Use

15)

Serienschaltbar

15)

Yes / Ja

Yes / Ja

Yes / Ja

Yes / Ja

Dimensions

16)

(WxHxD) Abmessungen

16)

(BxHxT)

nom. 40x124x117mm 40x124x117mm 62x124x117mm 62x124x117mm

Weight Gewicht

max. 500g; 1.1lb

500g; 1.1lb

750g; 1.65lb

750g; 1.65lb

Approvals Zulassungen

Ж 17)

Ж 17)

Ж 17)

Ж 17)

Limited Warranty

Gewährleistung

Years

/

Jahre 1 1 1 1

1) All parameters are specified at 3x400Vac (XLE240E-3, XLE240F-3) or 2x400Vac (XLE96B-2,

XLE120E-2) input voltage, symmetrical phase voltages, nominal output current, 25°C ambient and
after a 5 minutes run-in time unless otherwise noted. Mounting orientation: input terminals on the
bottom and output terminals on top.

2) The PowerBoost is continuously allowed up to an ambient of 45°C. Above that temperature,

do not use the PowerBoost longer than 1 minute every 10 minutes.

3) 50-Ohm measurement, bandwidth 20MHz
4) Input inrush current electronically limited and is temperature independent.
5) Use a battery or similar DC source. Connect + pole to L1 and - pole to L2. Terminal L3 remains

unused. Terminal screw of L3 must be securely tightened. Use appropriate external fuses in the +
and – line which are suitable for the DC-voltage (e.g. KLKD from Littelfuse). Additional tests might
be necessary when the complete system hast to be approved according to UL 508 or UL60950-1.

6) At nominal load and nominal input voltage.
7) At nominal load and the lower end of the input voltage.
8) Do not energize while condensation is present.
9) PE connection required (Ground).
10) Output shut-down with automatic restart attempts.
11) PE Leakage current at 3x440Vac, 50Hz / 3x528Vac, 60Hz, TT/TN-mains.
12) Loads such as decelerating motors and inductors can feed voltage back to the output of the

power supply. The figure represents the maximum allowed feed back voltage

13) Parallel use for a higher output power is allowed up to an ambient temperature of +45°C. A fuse (or

diode) on the output is required if more than three units are paralleled.

14) Set jumper on the front to “Parallel Use”. A fuse (or diode) on the output is required if more than

three units are paralleled.

15) Use only power supplies of the same type. The total output voltage should not exceed 150Vdc.
16) Depth without DIN-rail.
17) See datasheet or markings on the unit.

1) Alle Werte gelten bei 3x400Vac (XLE240E-3, XLE240F-3) oder 2x400Vac (XLE96B-2,

XLE120E-2), symmetrische Phasenspannung, Nennausgangsstrom, 25°C Umgebung und nach
einer Aufwärmzeit von 5 Minuten, wenn nichts anderes angegeben ist. Einbaulage: Eingang
unten und Ausgang oben.

2) Der PowerBoost kann bis 45°C dauerhaft entnommen werden. Über 45°C darf der PowerBoost

nicht länger als 1 Minute alle 10 Minuten wiederholt werden.

3) 50-Ohm Messung, Bandbreite 20MHz
4) Der Einschaltstromstoß ist elektronisch begrenzt und temperaturunabhängig.
5) Geeignet sind Batterien oder ähnliche Quellen. Den + Pol an L1 und - Pol an L2 anschließen.

L3 Anschluss bleibt offen, L3 Klemme muss geschlossen werden. Bei DC-Betrieb sind in der +
und - Zuleitung externe Sicherungen vorzusehen, die für die angelegte DC-Spannung geeignet
sind (z.B. KLKD von Littelfuse). Bei einer Zulassung des Gesamtsystems nach UL 508 oder UL
60950-1 können zusätzlich Prüfungen erforderlich werden.

6) Bei Nominallast und Nenneingangsspannung.
7) Bei Nominallast und dem unteren Ende der Eingangsspannung.
8) Nicht betreiben, solange das Gerät Kondensation aufweist.
9) PE Verbindung erforderlich.
10) Ausgang schaltet ab und macht regelmäßig automatische Startversuche.
11) Erd-Ableitstrom bei 3x440Vac, 50Hz / 3x528Vac, 60Hz, TT/TN-Netze.
12) Bremsende Motoren oder Induktivitäten können Spannung zum Ausgang des Netzteils

rückspeisen. Der Wert gibt die max. zulässige Rückspeisespannung an.

13) Parallelschaltung zur Leistungserhöhung ist bis zu einer Umgebungstemperatur von +45°C

erlaubt. Bei mehr als drei Geräten eine Sicherung oder Diode zur Entkopplung verwenden.

14) Steckbrücke an der Front des Gerätes auf „Parallel Use“ umstellen. Bei mehr als drei Geräten

wird eine Sicherung oder eine Diode zur Entkopplung benötigt.

15) Nur gleiche Geräte bis zu einer Gesamtspannung von 150Vdc.
16) Tiefe ohne DIN-Schiene.
17) Siehe Datenblatt oder Prüfzeichen auf dem Gerät.

Installation

Use DIN-rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm. Mounting
orientation must be output terminals on the top and input terminals on the bottom. For other
orientations see datasheet. Do not obstruct air flow as the unit is convection cooled. Ventilation
grid must be kept free of any obstructions. The following installation clearances must be kept
when power supplies are permanently loaded with more than 50% of the nominal current::

Left / right: 5mm (15mm in case the adjacent device is a heat source)

40mm on top, 20mm on the bottom of the unit.

Installation

Geeignet für DIN-Schienen entsprechend EN 60715 oder EN 50022 mit einer Höhe von 7,5 oder
15mm. Der Einbau hat so zu erfolgen, dass der Eingang sich unten und die Ausgang sich oben
befindet. Für andere Einbaulagen siehe Datenblatt. Luftzirkulation nicht behindern! Das Gerät ist
für Konvektionskühlung ausgelegt. Es ist für ungehinderte Luftzirkulation zu sorgen. Folgende
Einbauabstände werden bei dauerhafter Belastung >50% des Nennstromes empfohlen:

Links / rechts: 5mm (15mm bei benachbarten Wärmequellen)

Oben: 40mm, unten 20mm vom Gerät.

Input Fuses

Internal input fuse: T3.15A (H.B.C.), not user accessible. The unit is tested and approved for
branch circuits up to 32A. An external protection is only required if the supplying branch has an
ampacity greater than this, however, in some countries local regulations might apply. Check local
codes and requirements. If an external fuse is necessary or utilized, minimum requirements need
to be considered to avoid nuisance tripping of the circuit breaker. A minimum value of 6A B- or 3A
C-Characteristic breaker should be used.

Sicherungen am Eingang

Das Gerät besitzt eine T3,15A (H.B.C.) Eingangssicherung, die nicht anwenderzugänglich ist. Das
Gerät ist geprüft und zugelassen zum Anschluss an Stromkreisen bis max.32A. Ein zusätzlicher
externer Schutz ist nur erforderlich, wenn der Speisestromkreis mit einem höheren Wert
abgesichert ist oder nationale Richtlinien es vorschreiben. Falls ein externes Schutzelement
verwendet wird, soll dieses nicht kleiner als 6A B- oder 3A C-Charakteristik sein, um ein
fehlerhaftes Auslösen zu vermeiden.