Iv. conversion module wiring diagram – Rockwell Automation 1492-CM800-LD005 Field Wire Conversion Module for Modicon B807-132 to 1756-IA32 User Manual

Page 2

Advertising
background image

(2)

10000021868

(Version 00)

1756-IA32

1492-CABLE003Z

1492-CM800-LD005

Conversion: B807-132 to 1756-IA32 with 1492-CM800-LD005

B807-132 Swing Arm

Conversion Module Installation and Application Considerations

The input delay times for the B805-016 module versus 1756-IA16 module are as follows:

B807-132

1756-IA32

a) Off-to-On Delay

6ms

10ms (plus selectable filter)

b) On-to-Off Delay

12ms

8ms (plus selectable filter)

The B807-132 has 4 groups (allowing 4 separate power supplies) and the 1756-IA32 has 2 groups. This module/cable

combination ties Groups 1 & 2 from the B807-132 to Group 0 on the 1756-IA32 and it ties Groups 3 & 4 from the B807-132
to Group 1 on the 1756-IA32. Field wiring modification must be made to accommodate this if multiple supplies were used. If
4 supplies were used, 2 must be removed.

Refer to your B807-132 and 1756-IA32 Installation Manual wiring schematics and diagrams for more details.

[Reference Doc: 41170-754 (Version 03)]

IV. Conversion Module Wiring Diagram

The following diagram shows the connections from the existing B807-132 swing-arm, through the conversion module,
1492 cables and to the 1756-IA32 input module. The diagram can be used as an aid in possible system troubleshooting.

18

L2-0

IN-0

1

IN-16

19

IN-1

2

IN-17

20

IN-2

3

IN-18

21

IN-3

4

IN-19

22

IN-4

5

IN-20

23

IN-5

6

IN-21

24

IN-6

7

IN-22

25

Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green

IN-7

8

1
2
3
4

3

5

22

6

4

7

23

8

5

9

24

10

6

11

25

12

7

13

26
8

15

27

16

9

17

28

18

10

19

29

20

14

12

21

31

22

13

23

32

24

14

25

33

26

15

27

34

28

16

29

35

30

17

31

36

32

18

33

37
19

35

38

36

2

37

30

38
39
40

34

L2-1

36

IN-23

26

IN-8

9

IN-24

27

IN-9

10

IN-25

28

IN-10

11

IN-26

29

IN-11

12

IN-27

30

IN-12

13

IN-28

31

IN-13

14

IN-29

32

IN-14

15

IN-30

33

Orange/Green
Black/White/Red
White/Black/Red
Red/Black/White
Green/Black/White
Orange/Black/White
Blue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/Blue

IN-15

16

IN-31

34
17

L2-0

White/Red/Blue
Black/White/Green
White/Black/Green
Red/White/Green

L2-1

35

Input 1

Input 17

Input 2

Input 18

Input 3

Input 19

Input 4

Input 20

Input 5

Input 21

Input 6

Input 22

Input 7

Input 23

Input 8

Input 24

Input 9

Input 25
Input 10
Input 26
Input 11
Input 27
Input 12
Input 28
Input 13
Input 29
Input 14
Input 30
Input 15
Input 31

2

Input 16
Input 32

1
20
21
40

Not Used
Not Used
Not Used
Not Used

Group 1 Neutral
Group 3 Neutral

11
39

Group 2 Neutral
Group 4 Neutral

L1

L2

There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and output module). Read and understand these
considerations before installation.

WARNING

1492-CM800-LD005 Conversion Module

De-energize and lockout any and all power to all I/O field devices connected to the Modicon 800 I/O
housing, and the power to the 800 I/O housing itself. Ensure all power is de-energized and locked out to
any device in the control cabinet where the conversion is to be performed. Ensure work is performed by
qualified personnel.

WARNING