Hold-up time – Rockwell Automation 1606-XLP15A Power Supply Reference Manual User Manual

Page 7

Advertising
background image

All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

Rockwell Automation Publication 1606-RM019A-EN-P — March 2014

7

Bulletin 1606 Switched Mode Power Supplies

7. Hold-up Time

AC 100V

AC 120V

AC 230V

Hold-up Time

typ.

61ms

93ms

340ms

at 5V, 1.5A, see Fig. 7-1

typ.

29.5ms

45ms

186ms

at 5V, 3A, see Fig. 7-1

Note: At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is also on at this time.

Fig. 7-1 Hold-up time vs. input voltage

Fig. 7-2 Shut-down behavior, definitions

0

25

50

125

150ms

85

120

155

190

230Vac

Input Voltage

Hold-up Time

75

100

a) 5V 1.5A typ.

b) 5V 1.5Amin.
c) 5V 3A typ.
d) 5V 3A min.

a

b

c

d

- 5%

Hold-up Time

Zero Transition

Output
Voltage

Input
Voltage