Wiring – Rockwell Automation 1397 400-600 Hp Inverter Fault Circuit Breaker - IFB600 User Manual

Page 6

Advertising
background image

1397 Inverting Fault Circuit Breaker

6

1397-5.29 September, 1998

Drive

Motor A1

A1

Motor
Armature

Motor A2

Motor S1

Series Field

Motor S2

1 > Any other customer interlocks
must be connected in series
to terminals 9 and 11.

A2

S2

MOT

DRV

Inverting Fault Breaker

Inverting Fault Breaker
Aux Contact

1 > To regulator board
terminals 9 & 11

A2/S1

DB

M

M

M

Removable Link
Not Removed

Disconnect
existing A2
at Power I/F
PC Board

To Power I/F
PC Board A2

Figure 4.
Inverting Fault Circuit Breaker
with Series Field (S1 to A2)

Wiring

1

Refer to Figure 4. Connect motor series field lead S2 to Inverting
Fault Circuit Breaker terminal MOT. (See Figure 9 for location
of the breaker’s MOT terminal. Terminate the breaker side of the
leads with lugs of the appropriate gauge.

If you are using the Inverting Fault Circuit Breaker with a Series
Field (S1 to A2):

2

Using wire the same gauge as the motor leads, connect Inverting
Fault Circuit Breaker terminal DRV to drive output terminal S2.
(see Figure 9 for the location of the breaker’s DRV terminal.)
Terminate the breaker side of the wires with lugs of the
appropriate gauge.

3

Connect motor armature lead A1 to drive terminal A1.

Proceed to "Wire Assembly Connections."