Wiring – Rockwell Automation 1397 400-600 Hp Inverter Fault Circuit Breaker - IFB600 User Manual

Page 7

Advertising
background image

1397 Inverting Fault Circuit Breaker

7

1397-5.29 September, 1998

Drive

M

A1

Motor A1

M

Motor
Armature

Removable Link
Removed

Motor A2

Motor S1

Motor S2

Series Field

Customer supplied wire
Size to same gauge
as DB kit leads.

DRV

S2

MOT

A2

A2/S1

Inverting Fault Breaker
Aux Contact

1 > Any other customer interlocks
must be connected in series
to terminals 9 and 11

1 > To Regulator board
terminals 9 & 11

M

Disconnect
existing A2
at Power I/F
PC board

To Power I/F
PC board A2

Figure 5.
Inverting Fault Circuit Breaker
with a Series Field and Dynamic Braking

Wiring

If you are using the Inverting Fault Circuit Breaker with a Series
Field (S1 to A2) and Dynamic Braking:

1

Refer to Figure 7. Remove the removable link (bus section
connected to drive output terminal A2/S1) by removing the four
nuts and bolts that hold it in place. You may need to dismount
the drive in order to gain access to the removable link. If so,
re-mount the drive after the link has been removed.

2

Refer to Figure 5. Connect motor series field lead S2 to Inverting
Fault Circuit Breaker terminal MOT. (See Figure 9 for the
location of the breaker’s MOT terminal.) Terminate the breaker
side of the leads with lugs of the appropriate gauge.

3

Using wire of the same gauge as the motor leads, connect
Inverting Fault Circuit Breaker terminal DRV to drive output
terminal S2. (See Figure 9 for the location of the breaker’s DRV
terminal.) Terminate the breaker side of the wires with lugs of
the appropriate gauge.

4

Using wire the same gauge as the DB kit leads, connect motor
armature lead A1 to drive terminal A1.

Proceed to "Wire Assembly Connections".

4

Using wire the same gauge as the DB kit leads, connect motor
armature lead A1 to drive terminal A1.

5

Connect motor armature lead A1 to drive terminal A1.