Air Flow Transmitter 3

Publication 1414-IN001A-EN-P - October 2005

Install Air Flow Transmitter

The transmitter is mounted in such a way that the airflow passes the sensor head.
The power supply cables to the transmitter should be kept separated from high
voltage lines where heavy transients may occur.

The transmitter can be mounted in airflow channels with a diameter or channel
width of 100 to 370 mm (4 in to 15 in)

Wire and Connect Air Flow Transmitter

The length of the cable is not critical. Avoid placing it in parallel with other cables,
which may induce electrical noise on the voltage signal and thus disturb the
function of the transmitter.

The best installation is obtained with a separate cable to the transmitter. It is
recommended to use a shielded cable to the transmitter as this improves immunity
against noise when it is used in light-industrial areas. The shield should be
terminated at the supply point but not terminated at the transmitter.

6 5 4

3 2 1

- +

24 VAC

16-30 VDC

Flow 4-20Ma

GRD

Flow 0-10VDC

Temp 0-10VDC

20

4

10

16 m/s (3150 ft/min)
8 m/s (1575 ft/min)

0
0

mA

V out(dc)

1

3

2

4

6

5

+ 24 VDC -

ANL IN 0 +

ANL IN 0 -

Analog Current Input

ANL COM

Loop power supply

F

lo

w

, 4-

20

m

A

Te

m

p

0

-1

0

V

F

low

, 0-

1

0

V

G

ro

und

Po

w

e

r

2

4

VAC

,

16

-3

0

V

D

C

- +

Air Flow Transmitter

Wiring Diagram

Output Signals Scales

Dimensions

Wire to a Programmable Controller