Post-installation

The module is delivered with the range set at 0.5 to 8 m/sec (100 to 1575 ft/min). If
jumper SW1 is removed on the printed circuit board, the range 0.5 to 16 m/sec (100
to 3150 ft/min) is obtained.

Maintenance

As the thermal measuring principle is based on the cooling principle of the air, dirt
accumulation on the sensor will reduce the measuring accuracy. If the transmitter is
used in dirty air, the sensor head should be cleaned at suitable intervals.

Specifications

All other trademarks are the property of their respective holders, and are hereby acknowledged.

Air Flow Transmitter Specifications

Specification

Value

Airflow speed

0.5…8 m/s (100…1575 ft/m, 0.5…16 m/s (100…3150 ft/m)

Standard current signal

4…20 ma (loop resistance < 500

Ω)

Standard voltage signal

0…10V (max. 5mA)

Air temperature

–10ºC…+60ºC (+14°F…140°F)

Ambient temperature

–20ºC…+50ºC (-4°F…+122°F)

AC voltage supply

24V ac ±10% (120 ma)

DC voltage supply

16…30V dc (80 ma)

Absolute accuracy

±5% of full scale

Rise time

20 sec

Time constant

5 sec

Depth of insertion in channel

50…200 mm (2…8 in.)

Dimensions (HxWxD)

80 x 80 x 55 mm(3.15 x 3.15 x 2.17 in)