VIII. Appendix A - 800 Housing to 1756 Chassis Conversion System Selection Process

1) Determine the number of 800 I/O modules actually used in the 800 I/O Housing to be converted to 1756 I/O.
2) Review the data in Column 5 from the below table, and select a 1756 I/O Chassis which meets your conversion

needs from Step 1. Ensure the information from the I/O Conversion module table is reviewed first since in some
cases, two 1756 modules are needed to replace one 800 I/O module.

3) Once the 1756 Chassis is selected, refer to Column 7 and select the Conversion Assembly.

One chassis slot required for the ControlLogix processor or a remote I/O adapter type module.

The footprint and mounting dimensions of the 1492 Conversion Assembly (base plate and cover plate) match those of the

Modicon I/O Housing.

Width dimension includes the 1756 Chassis power supply.

Surplus Chassis width as compared to the 800 I/O Housing is divided equally when mounting it on the Conversion Assembly.

Mounting holes for the 1756 I/O Chassis are pre-drilled and pre-tapped into the Conversion Assembly cover plate.

Modicon is a Registered Trademark of Group Schneider

AS-H810-xxx

AS-H819-103

AS-H819-209

AS-H819-100

AS-H827-103

AS-H827-209

AS-B827-100

Modicon 800 I/O

Housing Cat Number

1492-MUA4-MB3

1492-MUA7-A10-

MB4679 

1492-MUA10-A13-

MB81011 

Conversion Assembly

Catalog Number

3

4

6

7

8

10

11

10.25”

17.5”

17.5”

17.5”

27.1”

27.1”

27.1”

10.25”

A7 = 14.49”

A10 = 19.02”

A7 = 14.49”

A10 = 19.02”

A7 = 14.49”

A10 = 19.02”
A10 = 19.02”

A13 = 23.15”
A10 = 19.02”

A13 = 23.15”
A10 = 19.02”

A13 = 23.15”

1756 Chassis

Width 

Dimension

3

A7 = 6, A10=9

A7 = 6, A10=9

A7 = 6, A10=9

A10 = 9, A13=12

A10 = 9, A13=12

A10 = 9, A13=12

1756 I/O Chassis

Catalog Number

1

7

2

3

6

5

4

1756-A4

1756-A7

or

1756-A10

1756-A10

or

1756-A13

VII. 1492-CM800-LD011 Conversion Module Specifications

(Operating specifications are when installed in the Conversion System base / cover-plate assembly)

Specification

Value

Dimensions

288.9 mm (height) x 139.7 mm (depth) x 44.5 mm (width)

11.37 in. (height) x 5.5 in. (depth) x 1.75 in. (width)

Approximate Shipping Weight

300g (0.66 lbs) (includes carton)

Storage Temperature

-40 to +85°C (-40 to +185°F)

Operating Temperature

0 to 55°C (32 to 131°F)

Operating Humidity

5 to 95% at 55°C (non-condensing)

Shock
Non-operating

Operating


50g

30g

Operating Vibration

2g @ 10-500Hz

Maximum Operating Voltage

150 Vdc

Fusing

Two, 4 Amp, 5 x 20 mm

Max. Module Operating Current

Per Point:
Per Module:

2 Amps (1492-CABLE connection pins are limited to 2A per pin)

12 Amps

Agency Certifications


UL Classified: Under UL File Number E113724

CSA
CE: compliant for all applicable directives

Pollution Degree

2

Environmental Rating

IP20

Max. Number

of 800 Housing

Slots for I/O

800 Housing

Width

Dimension

Max. Number

of 1756 Chassis

Slots for I/O

Refer to the Wiring Diagram(s) for