Installation – Rockwell Automation 1397 400-600HP AC Line Disconnect Inst. User Manual

Page 4

Advertising
background image

1397 600HP AC Line Disconnect

4

1397-5.30 July, 1998

BLOWER MOTOR
STARTER KITS

283

5FU

4FU

282

281

288

289

ON

M8 Bolt

and Lock-

washer

M8 Bolt

and Lock-

washer

Cover

Screw

Cover

Screw

7/16" Flat Washer

7/16" Split Lockwasher

7/16" x 1" Bolt

— (6) Places —

Bus Bar
(top)

M12 Nuts

— (6) Places —

Bus Bar
(bottom)

Adapter

M5

×

20

mm Screw

and M5 Toothed

Lockwasher

Installation

9

While holding the spacer and adapter plate in place, pick up the
disconnect and position it over the threaded holes on the drive’s
mounting panel.

11

Install the M5

×

20mm

phillips head screw and M5
toothed lockwasher where
the screw was removed in

Step 4

. Torque to 2.8 N-m

(25 lb-in.). This establishes
a ground connection for the
disconnect switch.

13

Replace the disconnect’s bottom lug cover and
tighten the (2) captive screws to secure it in place.

14

Replace the plastic line fuse cover removed in

Step

1

and tighten the (2) screws at the bottom to secure

it in place.

12

Remove the disconnect’s lower lug cover by
loosening the (2) captive cover screws. Attach a bus
bar between the drive’s right-side line fuse
connector and the disconnect’s right-side load
connector. Use (2) 7/16" flat washers, (2) split
lockwashers

&

(2) 1" bolts for the disconnect

connection. Use two of the M12 nuts removed in

Step 3

for the line fuse connection. Repeat this

procedure to attach the remaining bus bars. Tighten
the bus bar to disconnect bolts to 34N-m
(300lb.-in.). Tighten the bus bar to line fuse
terminal nuts to 24 Nm (210 in-lb).

10

Attach the disconnect by hand tightening the (2) bolts
inserted previously. After the bolt threads catch in
the bolt holes, insert the remaining (2) mounting
bolts

&

lockwashers. Tighten all bolts to 14N-m

(125lb.-in.).