Installation

21

With the disconnect in the OFF position, remove the
lockout and tag and restore incoming power to the
drive. The motor should not be operating at this
time.

Set the line disconnect switch to the ON position.
To set the switch, first move it into position 0 (down)
and then move it to position 1 (up). The drive should
power up.

Test the installation by setting the disconnect to
OFF (position 0) and measuring the voltage at
terminals 181, 182 and 183. All three terminals
should be at 0VAC, line-to-line and
line-to-ground. If not, remove power to the drive
and recheck all disconnect connections.

Reset the disconnect switch by moving it to the
ON position.