Setup, J6 j7 – Rockwell Automation 1397-L11 I/O Expansion Card User Manual

Page 7

Advertising
background image

1397 – 5.19 August, 2000

1397 I/O Expansion Card

7

Digital Input Settings

To configure the I/O Expansion Card’s digital inputs, only
parameters

1

must be set. Each of the card’s (5) digital inputs is fixed

and listed below. The drive will recognize a change of state (e.g. 0-to-
24V DC or 24-to-0V DC) if it is applied for longer than 20mS.

Terminal 60

2

Terminal 59

2

Preset Speed A

Preset Speed B

Speed Reference Selected

3

0

0

Determined by Standard Terminal Block
Input 6 (Reference Select)

0

1

Preset Speed 1 (P.087)

1

0

Preset Speed 2 (P.088)

1

1

Preset Speed 3 (P.089)

Terminal 63

2

Terminal 62

2

MOP Increment

MOP Decrement

Effect of MOP Output (P.015)

4

0

0

No Change

0

1

Decrement at MOP Decel Time Rate (P.085)

1

0

Increment at MOP Accel Time Rate (P.084)

1

1

No Change

Terminal 64

2

OCL Enable

Turns Outer Control Loop (OCL) on or off based
on the drive’s running state and P.121 — OCL
Enable Src.

5

1

For a detailed description of these Digital Input Parameters, refer to the parameter descriptions
in the 1397 User manual.

2

Depending upon the application, terminal 58 (+24V DC), 61 (+24V DC), or 65 (24V COM) is
used with this digital input terminal.

3

Refer to the Speed/Trim Reference Select Firmware Block Diagram in Appendix A of the
1397 User Manual for additional information.

4

Refer to the I/O Expansion Inputs Firmware Block Diagram in Appendix A of the 1397 User
Manual for additional information.

5

Refer to the Outer Control Loop Firmware Block Diagram in Appendix A of the 1397 User
Manual for additional information.

Preset B

Preset A

+24V

DC

MOP Decrement

MOP Increment

OCL Enab

le

24V COM

53

54 55

56

57

59

60

61

62

58

63

64

65

+24V

DC

J6

J7

Setup

(continued)