8

1397 I/O Expansion Card

1397 – 5.19 August, 2000

Analog Input Settings

The I/O Expansion Card supports two analog inputs — Anlg In 3
and Anlg In 4.

Anlg In 3 has (4) parameter settings

1

and can be jumpered to accept

(4) types of input signals

3, 4, 5

.

Anlg In 4 has (3) parameter settings

1

and only accepts a bipolar DC

voltage.

Analog inputs can be scaled to use DC voltage signals as low as 4.5V
DC (5V DC ±10%), but the maximum resolution of 0.024% is only
obtained when a full scale input signal is used. Analog inputs are read
every 20mS.

Parameter No.

Parameter Name

Terminal Nos.

P.003

Anlg In 3

50 and 51

2

P.004

Anlg In 4

52 and 53

2

P.133

Anlg In 3 Type

P.134

Anlg In 3 Zero

P.132

Anlg In 3 Gain

P.136

Anlg In 4 Zero

P.135

Anlg In 4 Gain

1

For a detailed description of these Analog Input Parameters, refer to the parameter descriptions
in the 1397 User manual.

53

54 55

56

57

59

60

61

62

58

J6

J5

38

39 40

41

42

43

44

50

51

52

Anlg In 3

Anlg In 4 +

Anlg In 4

Anlg In 3 +

Setup

(continued)

Dig Out 1 Com

Dig Out 2

Dig Out 2 Com

Dig Out 1

66

67

68

69

J9

J8

Digital Output Jumper and Parameter Settings

To configure the I/O Expansion Cards digital outputs, only
parameters must be set

1

. The cards (2) digital outputs can be sourced

from various drive functions and will hold their state for a minimum
of 20mS.

Parameter No.

Parameter Name

Terminal Nos.

P.155

Dig Out 1 SRC

66 and 67

P.157

Dig Out 2 SRC

68 and 69

P.156

Dig Out 1 Type

2

P.158

Dig Out 2 Type

2

1

For a detailed description of these Digital Output Parameters, refer to the parameter descriptions
in the 1397 User manual.

2

If Parameters 156 and/or 158 are configured as normally closed contacts, they will act as
normally open contacts during a drive power cycle.