R m otor starter kits, 4b 4b 4a 4c – Rockwell Automation 1397 Blower Motor Starter Inst. User Manual

Page 6

Advertising
background image

1397 Blower Motor Starter

6

1397-5.20 April, 1998

REMOVE

DON'T REMOVE

R M

OTOR

STARTER

KITS

283

5FU

4FU

282

281

183

182

181

Man|Aut

16

A

18

13

15

6

4

2

R

R

0

95

96

97

98

T1

T2

T3

5

-

13

2

-2

T1

3

-4

T2

4

-6

T3

5

-

14

REPLACE WITH

LITTLEFUSE, TYPE CCMR, 600V 2.5A

13FU

14FU

15FU

2

-1

L1

3

-3

L2

4

-5

L3

P8

P8

L2

L1

288

289

3

3

4b

1

2

2

4a

4c

4c

Man|Aut

16

A

18

13

15

6

4

2

R

R

0

95

96

97

98

T1

T2

T3

5

-

13

2

-2

T1

3

-4

T2

4

-6

T3

5

-

14

REPLACE WITH

LITTLEFUSE, TYPE CCMR, 600V 2.5A

13FU

14FU

15FU

2

-1

L1

3

-3

L2

4

-5

L3

OFF

R MOTOR

STARTER KITS

283

81

82

83

5FU

4FU

!

DANGER

RISK OF ELECTRICAL SHOCK. DISCONNECT INPUT
POWER BEFORE SERVICING EQUIPMENT.

P/N 33145

282

281

288

289

181/L1

182/L2

183/L3

L3

400-600HP/460V
Drive Installation
Single Blower Motor Applications

2

Remove and lock-out all incoming power to the
drive. Loosen the (2) phillips head screws on the
molded fuse block and slide the kit’s keyed
mounting slots over the screws — the kit may
be mounted at either location on the fuse block.
Torque to 6.22 N-m (55 lb-in.).

4

Loosen the harness fastener screw .

Connect and route the leads of the long 3-conductor wire harness from the bottom of the Blower Motor Starter
under the harness fastener to the top of the line fuses as shown .

Hand tighten the harness fastener screw to secure the harness.

3

Locate one of the P8 jumper connector assemblies. Remove the jumper plug and connect jumper assembly P8 to the
Blower Motor Starter’s matching connector. For single Blower Motor Starter applications, leave the other P8 jumper
connector assembly alone.

1

Disconnect wires 181, 182 & 183 from the back
of the Blower Motor Starter fuse block and discard
them.

Important:

Each blower motor requires it’s own Blower Motor

Starter. 400-600HP 1397 drives have provisions for mounting
up to (2) Blower Motor Starters. For single blower motor
applications, the starter kit may be mounted at either location
on the fuse block. For applications requiring more than (2)
blower motors, consult the factory.

4b

4b

4a

4c