1+1 redundancy up to 40a, N+1 redundancy, example with 120a – Rockwell Automation 1606-XLSRED80 Power Supply Reference Manual User Manual

Page 16

Advertising
background image

All parameters are specified at 24V, 80A output current, 25ªC ambient and after a 5 minutes run-in time, unless noted otherwise.

16

Rockwell Automation Publication 1606-RM011A-EN-P — February 2014

Bulletin 1606 Switched Mode Power Supplies

17.4. 1+1 Redundancy up to 40A

1+1 Redundancy up to 40A requires two 40A power supplies and one 16060-XLSRED80 redundancy module.

Fig. 17-1 Wiring diagram, 1+1 Redundancy, 40A output current

L1
L2

PE

L3

1606-
XLSRED80

Redundancy

Module

+

-

+

-

Input

1

Input

2

Output

L1 L2 L3 PE

Power Supply

+ +

- -

24V, 40A

Parallel Use

Single Use

DC-

OK

40A

Load

Failure

Monitor

I

I

I

I

I

I

L1 L2 L3 PE

Power Supply

+ +

- -

24V, 40A

Parallel Use

Single Use

DC-

OK

Note: Use separate mains systems for each power supply whenever possible.

17.5. N+1 redundancy, Example with 120A

n+1 Redundancy up to 120A requires four 40A power supplies and two 16060-XLSRED80 redundancy modules.

Fig. 17-2 Wiring diagram, n+1 Redundancy, 120A output current

1606-
XLSRED80

Redundancy

Module

+

-

+

-

Input

1

Input

2

Output

L1 L2 L3 PE

Power Supply

+ +

- -

24V, 40A

Parallel Use

Single Use

DC-

OK

120A

Load

Failure

Monitor

I

I

I

I

I

I

L1 L2 L3 PE

Power Supply

+ +

- -

24V, 40A

Parallel Use

Single Use

DC-

OK

1606-
XLSRED80

Redundancy

Module

+

-

+

-

Input

1

Input

2

Output

L1 L2 L3 PE

Power Supply

+ +

- -

24V, 40A

Parallel Use

Single Use

DC-

OK

L1 L2 L3 PE

Power Supply

+ +

- -

24V, 40A

Parallel Use

Single Use

DC-

OK

I

I

I

I

I

I

L1
L2

PE

L3

Note: Whenever possible, use separate mains systems for each power supply.