Power losses – Rockwell Automation 1606-XLSRED80 Power Supply Reference Manual User Manual

Page 5

Advertising
background image

All parameters are specified at 24V, 80A output current, 25ªC ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM011A-EN-P — February 2014

5

Bulletin 1606 Switched Mode Power Supplies

4. Power Losses

DC 24V

Power losses

typ.

2.7W input:

2x20A

typ.

8.3W

input: 2x40A

typ.

3.6W input:

1x40A,

(only one input is connected to input voltage)

Standby power losses

typ.

0.35W

at no output current,
(only one input is connected to input voltage)

typ.

0.7W

at no output current,
(both inputs are connected to input voltages)

Fig. 4-1 Power losses when both inputs draw equal current

(typical n+1 or 1+1 redundant case, when the power supplies are set into “parallel use” mode)

Power Losses, typ.

0

0

10

20

60

2

4

6

8

10W

80A

50

30

40

70

Output Current

A... 25°C

B... 60°C

A

B

Output

V

A

24V,40A

+

-

"Parallel
Use"

V

A

I

1

I

2

U

1

U

2

A

V

I

OUT

U

OUT

I

1

I

2

=

U

2

U

1

L

=

osses

U

1

=

U

OUT

-

*

I

1

+

)

(

*

U

2

*

I

2

I

OUT

24V,40A

+

-

"Parallel
Use"

Variable

Load,

0-80A

XLSRED80

Input 1

Input 2

Output

Fig. 4-2 Power losses when only one input is used

Power Losses, typ.

0

0

5

10

30

1

2

3

4

5W

40A

25

15

20

35

Output Current

A... 25°C

B... 60°C

A

B

Losses

U

1

=

U

OUT

-

*

I

1

*

I

OUT

Output

V

A

24V,40A

+

-

I

1

U

1

A

V

I

OUT

U

OUT

XLSRED80

Input 1

Input 2

Output

Variable

Load,

0-40A

Note: As soon as voltage is applied on input 2, an additional 0.35W will be consumed. It does not matter whether this channel

contributes to the output current or not.