Coil replacement instructions, Installation instructions, E - doc – Rockwell Automation 1102C-COx93_DOx93 Vacuum Contactor (400A / 600A) User Manual

Page 2

Advertising
background image

Control-Pak

Line Terminals

1/4 Flat

Washer

1/4 Lock Washer

1/4" or 7mm Bolt

Coil

Terminals

Load Terminals

A1

A2

Coil Replacement Instructions

1. Disconnect all power cables (or bus work) and all control wiring to the contactor.
2. Remove the contactor from its mounted location. The contactor is best serviced in the benchtop position as shown.
3. Remove the cover attachment screws from the contactor and remove the cover (Figure 3A).
4. Disconnect the coil wire leads from the Control-Pak. Remove the Control-Pak from the contactor and set on benchtop (Figure 3B).
5.
While supporting the Main Housing, remove the Main Housing from the Baseplate by removing the (4) screws which hold the housing
to the Baseplate. A long phillips-head screwdriver (6" or longer) is needed as the four screws are in deep wells (holes) in the Main
Housing. Remove the shorter screws first. Separate the main housing assembly from the Baseplate and set it aside.

(Figure 3C).

Installation Instructions

The vacuum contactor may be used in any mounting plane. In any non-horizontal mounting plane, the top of the contactor should point up
(so that the label appears right-side up). Care should be taken to insure that the mounting hardware does not warp the mechanism frame.
If the surface of the contactor to which the contactor is mounted is twisted, shims should be used to correct the condition. Any appreciable
degree of end to end twist will result in phase to phase discrepancies and timing of the main contact could cause increased pickup in
control voltage values.

1. Figure 1 illustrates the field terminals for line and load terminations. Mount the contactor with the hardware specified in Figure 2.
Loosely install the (4) mounting bolts into the intended mounting surface. Torque the mounting bolts to 50 - 75 lb-inches.
2. Connect control wires to the vacuum contactor control terminals A1 and A2 located on the Control-Pak using #18 to #12 gauge 75°C
stranded copper or tin stranded copper wire tightening screw terminals to 7 lb-inches torque.
3. Using 75°C wire copper cable, connect the line and load conductors to the main terminals (Figure 1) and proper phase rotation, tighten
the main terminal bolts to 132 lb-inches torque.
4. Check all connections for accuracy and mechanical connection before energizing.

42052-080

G. Ushakow

N/A

N/A

N/A

42052

1006490

1

INSTRUCTION SHEET

BULLETIN 1102C VACUUM CONTACTOR

CURRENT RATINGS 400A AND 600A

200V-1500V

2-20-04

Mark Jutz

2-20-04

D. Josef

2-20-04

2

9

REVISION

AUTHORIZATION

DIMENSIONS APPLY BEFORE

SURFACE TREATMENT

H

A

B

C

D

E

F

G

(DIMENSIONS IN INCHES)

TOLERANCES UNLESS

OTHERWISE SPECIFIED

REFERENCE

SHEET

OF

DWG.

B

DR.

CHKD.

APPD.

DATE

DATE

DATE

±

±
±

ANGLES:

.XXX:

.XX:

THIS DRAWING IS THE PROPERTY OF

THE ALLEN-BRADLEY CO. INC.

AND MAY NOT BE COPIED, USED OR

DISCLOSED FOR ANY PURPOSE EXCEPT

AS AUTHORIZED IN WRITING BY

THE ALLEN-BRADLEY CO. INC.

LOCATION : MILWAUKEE,

WISCONSIN

U.S.A.

SIZE

1

2

3

4

5

6

7

8

E - DOC

ATTENTION: If coil failure is suspected, check that secondary damage has not occurred that will render the contactor
non-repairable.

VACU

UM C

ONTA

CTO

R

FIGURE 3A

FIGURE 3B

FIGURE 1

FIGURE 2

(2)

VACU

UM C

ONTA

CTO

R

VAC

UUM

CON

TAC

TOR

VACUUM CONTACTOR

Control-Pak

This tab must

clear notch prior

to pushing

Control-Pak

downward.

Rotate retainer to

release Control-Pak

Advertising