Iv. conversion module wiring diagram, Module a module b – Rockwell Automation 1492-CM800-LD004 Field Wire Conv. Module for Modicon B806-032 to 1756-OA16 User Manual

Page 2

Advertising
background image

(2)

10000021863

(Version 00)

IV. Conversion Module Wiring Diagram

The following diagram shows the connections from the existing B806-032 swing-arm, through the conversion module, 1492
cables and to the 1756-OA16 output modules. The diagram can be used as an aid in possible system troubleshooting.

1756-OA16

1756-OA16

1492-ACABLE003X

1492-ACABLE003X

1492-CM800-LD004

Conversion: B806-032 to 1756-OA16 Qty 2 with 1492-CM800-LD004

B806-032 Swing Arm

1
2
3
4

3

5

22

6

4

7

23

8

5

9

24

10

6

11

25

12

7

13

26

8

15

27

16

9

17

28

18

10

19

29

20

14

12

31

13

32

14

33

15

34

16

35

17

36

18

37

19

38

21

11

Output 1

Output 17

Output 2

Output 18

Output 3

Output 19

Output 4

Output 20

Output 5

Output 21

Output 6

Output 22

Output 7

Output 23

Output 8

Output 24

Output 9

Output 25

Output 10

Output 26

Output 11

Output 27

Output 12

Output 28

Output 13

Output 29

Output 14

Output 30

Output 15

Output 31

Output 16

Output 32

39

20
2

Grp 1 Neut

40

1

30

Not Used

Grp 1 Hot

Not Used

1
2
3
4
5
6
7
8
9
10
11
12
13

15
16
17
18
19
20

14

MODULE

A

MODULE B

P1

P2

10

L1-0

OUT-0

1

OUT-1

2

OUT-2

3

OUT-3

4

OUT-4

5

OUT-5

6

OUT-6

7

OUT-7

8

OUT-8

11

OUT-9

12

OUT-10

13

OUT-11

14

OUT-12

15

OUT-13

16

OUT-14

17

OUT-15

18

Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green

L1-1

20

9

L2-0

19

L2-1

10

L1-0

OUT-0

1

OUT-1

2

OUT-2

3

OUT-3

4

OUT-4

5

OUT-5

6

OUT-6

7

OUT-7

8

OUT-8

11

OUT-9

12

OUT-10

13

OUT-11

14

OUT-12

15

OUT-13

16

OUT-14

17

OUT-15

18

Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green

L1-1

20

9

L2-0

19

L2-1

Grp 2 Neut

Not Used

Grp 2 Hot

Not Used

LOAD

L2

L1

Conversion Module Installation and Application Considerations

This configuration uses two (2) 1756-OA16 output modules to replace a single B806-032 output module. This may require the use

of a larger 1756 I/O Chassis. Ensure there is sufficient panel space to allow for this possibility.

The B806-032 module output current limits versus 1756-OA16 limits are as follows:

B806-032

1756-OA16 w/ 1492-CABLE003X

a) Current/Point

1A

0.5A

b) Current/Group

8A

2A

c) Current/Module

16A (32 pts)

4A (16 pts)

d) Surge Current/Pt 15A for 1 cycle

5A for 43ms

The B806-032 module did NOT provide fusing. The 1756-OA16 provides a single fuse per group.

 The 1492-CABLE003X current is limited to 2A per pin.

Refer to your B806-032 and 1756-OA Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output

module ratings are not exceeded.

[Reference Doc: 41170-753 (Version 03)]

There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and output module). Read and understand these
considerations before installation. In addition, refer to the current draw requirements of the existing
loads for this configuration to ensure they are within the current ratings of the 1756 output module.

WARNING

1492-CM800-LD004 Conversion Module

De-energize and lockout any and all power to all I/O field devices connected to the Modicon 800 I/O
housing, and the power to the 800 I/O housing itself. Ensure all power is de-energized and locked out to
any device in the control cabinet where the conversion is to be performed. Ensure work is performed by
qualified personnel.

WARNING

Refer to conversion module Specifications Section: Maximum Operating Voltage

Advertising