V. 1492-CM800-LD004 Conversion Module Specifications

(Operating specifications are when installed in the Conversion System base / cover-plate assembly)

Specification

Value

Dimensions

288.9 mm (height) x 139.7 mm (depth) x 44.5 mm (width)

11.37 in. (height) x 5.5 in. (depth) x 1.75 in. (width)

Approximate Shipping Weight

300g (0.66 lbs) (includes carton)

Storage Temperature

-40 to +85°C (-40 to +185°F)

Operating Temperature

0 to 55°C (32 to 131°F)

Operating Humidity

5 to 95% at 55°C (non-condensing)

Shock
Non-operating

Operating


50g

30g

Operating Vibration

2g @ 10-500Hz

Maximum Operating Voltage

125 Vac at 47 to 63 Hz

Max. Module Operating Current

Per Point:
Per Module:

2 Amps (1492-CABLE connection pins are limited to 2A per pin)

12 Amps

Agency Certifications



UL Classified: Under UL File Number E113724

CSA
CE: compliant for all applicable directives

Pollution Degree

2

Environmental Rating

IP20

Conversion Module Installation and Application Considerations

This configuration uses two (2) 1756-OA16 output modules to replace a single B806-032 output module. This may require the use

of a larger 1756 I/O Chassis. Ensure there is sufficient panel space to allow for this possibility.

The B806-032 module output current limits versus 1756-OA16 limits are as follows:

B806-032

1756-OA16 w/ 1492-CABLE003X

a) Current/Point

1A

0.5A

b) Current/Group

8A

2A

c) Current/Module

16A (32 pts)

4A (16 pts)

d) Surge Current/Pt 15A for 1 cycle

5A for 43ms

The B806-032 module did NOT provide fusing. The 1756-OA16 provides a single fuse per group.

 The 1492-CABLE003X current is limited to 2A per pin.

Refer to your B806-032 and 1756-OA Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output

module ratings are not exceeded.

[Reference Doc: 41170-753 (Version 03)]

Refer to the Wiring Diagram(s) for
current limits for a specific configuration.

NOTICE

1492-CM800-LD004 Conversion Module

De-energize and lockout any and all power to all I/O field devices connected to the Modicon 800 I/O
housing, and the power to the 800 I/O housing itself. Ensure all power is de-energized and locked out to
any device in the control cabinet where the conversion is to be performed. Ensure work is performed by
qualified personnel.

WARNING

Refer to conversion module Specifications Section: Maximum Operating Voltage