Chapter 2

Installation

Bypass Switch

Installation of the ProDySC with an external maintenance bypass is required to
avoid power interruptions to the critical loads during maintenance, service, or
testing. Mount the bypass close to the ProDySC to provide quick access and
visual coordination when testing or providing service. The 1608P bypass is a wall
mounted enclosure with a 3 position rotary switch. Its dimensions and mounting
locations are shown in

Figure 3

.

Figure 3 - 25A and 50A bypass mounting dimensions

Bypass Switch Modes

The 1608P bypass switch has three modes of operation and is configured as
shown in

Figure 4

Figure 4 - Bypass switch and mode operation

NORMAL Mode -

Power flows from the utility source

through the ProDySC to the load.

TEST Mode -

Power flows directly from the utility to

the load. ProDySC outputs are not connected to the
load. ProDySC inputs have power provided for testing
by a qualified technician.

BYPASS Mode -

Power flows directly from the utility

to the load. No power is present on ProDySC inputs or
outputs.

NOTICE: The 1608P bypass switch contacts are designed to make-before-break and will not
disrupt power to the load during any mode transitions. The switch has lockout/tagout (LOTO)
provisions.

12.00

305

16.75

425

4X .30

8

14.00

356

8.00

203

17.50

445