Fuse Rating Charts

Replace fuse with the same type or equivalent cross-referenced rating. You may
order these fuses through Rockwell Automation or the manufacturer listed.

Table 13 - DySC Fuse Ratings for 25A Unit

Table 14 - DySC Fuse Ratings for 50A Units

.

Table 15 - Bypass Switch Fuse Ratings

Fuse Reference

Fuse Location

Fuse Rating

Manufacturer Part Number

F1, F2, F3

Main Power Input

60A/500V

Mersen A50QS60-4

F7

Input Control Transformer

0.5A/600V

Mersen ATQR1/2

F4, F5, F6

Cross-Coupling Transformer

15A/600V

Mersen TRS15R

F8, F9, F10

(3 wire models only)

Neutral Forming Transformer

0.75A/600V

Mersen ATQR3/4

F17, F18

Output Control Transformer

2A/600V

Mersen ATQR2

F1, F2

(ER models only)

Extended-Run Module PCB (x3)

25A/600V

Mersen A60Q25-2

Fuse Reference

Fuse Location

Fuse Rating

Manufacturer Part Number

F1, F2, F3

Main Power Input

150A/500V

Mersen A50QS150-4

F7

Input Control Transformer

0.5A/600V

Mersen ATQR1/2

F4, F5, F6

Cross-Coupling Transformer

30A/600V

Mersen TRS30R

F8, F9, F10

(3 wire models only)

Neutral Forming Transformer

0.75A/600V

Mersen ATQR3/4

F17, F18

Output Control Transformer

2A/600V

Mersen ATQR2

F1, F2

(ER models only)

Extended-Run Module PCB (x6)

25A/600V

Mersen A60Q25-2

WARNING: De-energize the Bypass Switch by opening the upstream branch
circuit breaker before replacing a Bypass Switch fuse. Failure to comply with this
warning can result in injury or death

Bypass Cat. No.

Fuse Rating

Manufacturer Part Number

1608P-BP025A480V3

35A/600V

Bussmann LPJ-35SP

1608P-BP050A480V3

100A/600V

Bussmann DFJ-100