Rockwell Automation 1609-PSB1 Uninterruptible Power Supply Service Bypass Switch User Manual

Page 2

Advertising
background image

C

ONNECTING

P

OWER

Warning: Do not modify inlets or outlets. The SBP and UPS plugs and receptacles
should match. For more information, contact Rockwell Automation.

1. Non-Hardwired Panels

1. Plug SBP UPS output cord into UPS PDU panel.*

2. Plug UPS input cord to SBP UPS input receptacle.*

3. Plug customer equipment into SBP PDU panel.

4. Plug SBP into utility power outlet.

*Units with IEC receptacles: Use jumper cables.

2. Hardwired Panels

Attention: Wiring must be performed by a qualified electrician.

1. Switch input circuit breaker off.

2. SBP units that will be rack-mounted: Set SBP in the rack.

3. Unscrew and remove top access panel.

4. If using 1609-P5000E or 1609-P8000E with a hardwired UPS: Unscrew existing

terminal block wiring. Do not touch factory wiring (see

E

).

5. If using 1609-P5000E or 1609-P8000E with a hardwired UPS:

Unscrew and

remove rear input/output panel.

6. Remove circular knockouts from hardwiring input/output panel (see

A:

UO= UPS

Output; UI= UPS Input; AI= AC Input; LD= Load).

1609-PSB1 units: Also, remove circular knockouts from PDU output panel.

7. Connect wires to terminal blocks (see

B

). Adhere to all national and local

electrical codes.

8. Reinstall access panel.

9. Install hardwiring input/output panel.

10. SBP units that will be rack-mounted: Screw SBP into the rack.

A.

















41063-300-01(1)

B.

1609-PSB1









































41063-300-01(1)

T

ROUBLESHOOTING

Use the chart below to solve minor SBP installation problems. Also, refer to the UPS User
Manual Troubleshooting
section.

Problem and

Possible Cause

Solution

UPS

WILL NOT TURN ON AFTER

ON

BUTTON IS PUSHED

SBP handle is in ‘Bypass’ position.

Rotate the SBP handle to the ‘Normal’ position.

There is no power at UPS input.

Check that the power cables from the SBP to the utility power, and
from the SBP to the UPS Input are securely connected.

UPS is faulty or damaged.

Rotate the SBP handle into the ‘Test’ position. If the connected
equipment becomes energized, the UPS may be faulty. To confirm
this, refer to UPS User Manual Troubleshooting.

There is no power at the utility
power outlet.

Rotate the SBP handle into the ‘Test’ position. If the connected
equipment fails to become energized, the utility power outlet may be
faulty. Check the utility power supply by plugging a table lamp into
the suspect outlet. If the utility outlet fails to power the lamp, contact
qualified service personnel to restore power.

UPS

IS ONLINE

;

NOT POWERING ALL CONNECTED EQUIPMENT

SBP output circuit breaker tripped.

Reduce the load by unplugging equipment. Reset the breaker.

There is no power at SBP output.

Check that the power cable from the SBP to the UPS output is
securely connected.







































41063-300-01(1)

Advertising