Motor troubleshooting chart – Rockwell Automation 1329M AC Induction Motors, 56-5000 Frame, User Manual User Manual

Page 11

Advertising
background image

AC Induction Motors

11

The fuses and other protective devices are in proper condition.

All connections and contacts are properly made in the circuits
between the control apparatus and motor.

Motor Troubleshooting Chart

These instructions do not cover all details or variations in equipment
nor provide for every possible condition to be met in connection with
installation, operation or maintenance. Should additional information
be desired for the purchaser’s purposes, the matter should be referred
to the manufacturer.

Your motor service and any troubleshooting must be handled by
qualified persons who have proper tools and equipment.

Trouble

Cause

What To Do

Motor fails to start

Blown fuses

Replace fuses with proper type and rating

Overload trips

Check and reset overload in starter.

Improper power supply

Verify that power supplied agrees with motor nameplate and load factor.

Improper line connections

Check connections with diagram supplied with motor.

Open circuit in winding or control switch

Indicated by humming sound when switch is closed. Check for loose
wiring connections. Also verify that all control contacts are closing.

Mechanical failure

Verify that motor turns freely. Check bearings and lubrication.

Short circuited stator

Indicated by blown fuses. Motor must be rewound.

Poor stator coil connection

Remove end bells, locate with test lamp.

Rotor defective

Look for broken bars or end rings.

Motor may be overloaded

Reduce load.

Motor stalls

One phase may be open

Check lines for open phase.

Wrong application

Change type or size. Consult manufacturer.

Overload

Reduce load.

Low voltage

Verify that nameplate voltage is maintained. Check connection.

Open circuit

Fuses blown, check overload relay, stator and pushbuttons.

Motor runs and then dies
down

Power failure

Check for loose connections to line, to fuses and to control.

Motor does not come up to
speed

Not applied properly

Consult supplier for proper type.

Voltage too low at motor terminals because of
line drop.

Use higher voltage on transformer terminals or reduce load. Check
connections. Check conductors for proper size.

Starting load too high

Check load motor is supposed to carry at start.

Broken rotor bars or loose rotor

Look for cracks near the rings. A new rotor may be required as repairs
are usually temporary.

Open primary circuit

Locate fault with testing device and repair.

Motor takes too long to
accelerate and/or draws
high amp

Excessive load

Reduce load.

Low voltage during start

Check for high resistance. Adequate wire size.

Defective squirrel cage rotor

Replace with new rotor.

Applied voltage too low

Get power company to increase power tap.

Wrong rotation

Wrong sequence of phases

Reverse connections at motor or at switchboard.

Motor overheats while
running under load

Overload

Reduce load.

Frame or bracket vents may be clogged with
dirt and prevent proper ventilation of motor.

Open vent holes and check for a continuous stream of air from the
motor.

Motor may have one phase open

Check to make sure that all leads are well connected.

Grounded coil

Locate and repair.

Unbalanced terminal voltage

Check for faulty leads, connections and transformers.

Advertising