Install the Outside Air Temperature Transmitter

For best results locate the sensor on the north side of the structure high under an
eave to prevent incorrect readings from direct sunlight and damage due to the
elements. Mount the OSA enclosure with the sensor module facing down to
prevent the accumulation of dirt or water.

Wire/Connect the Outside Air Temperature Sensor

The wiring diagram shows typical connections to a controller. For 4 to 20 mA loop
signal, only the PWR and OUT terminals are used.

Field Calibration

The unit can be calibrated in the field by using precision resistor values equal to the
zero and span of the transmitter temperature range.

1. Disconnect the sensor from the transmitter and connect the resistor that

represents the zero value to the EXC and NEG terminals.