2. Adjust the ZERO pot until the desired output is achieved.
3. Connect the resistor that represents the span value to the EXC and NEG
terminals.
4. Adjust the SPAN pot until the desired output is achieved.
Repeat these steps until no further adjustment is required.
Specifications
All other trademarks are the property of their respective holders, and are hereby acknowledged.
TIP
If the unit uses a three-wire sensor, a jumper must be placed
between EXC and SEN.
Duct Temperature Sensor Specifications
Specification
Value
Operating Temperature Range
-50 … 50 ° C (-58 … 122 °F)
Wiring Connections
Terminal blocks
Enclosures
Metal 1/2 LBA
Sensor Types
1000
Ω platinum Class A 0.15°C , Class B 0.3°C, 0.1% FSO for the board