Chapter 3, Communications, Dry contacts – Rockwell Automation 1608P HC-DySC Installation Instructions, 200 A User Manual

Page 13: Figure 6 - access cover location, Ch 3 - communications, Chapter

Advertising
background image

Rockwell Automation Publication 1608P-IN004A-EN-P - September 2013

13

Chapter

3

Communications

Both dry contacts (relays) that indicate status and a Serial Communications Port
(RS-232) are available for monitoring the HC-DySC.

Dry Contacts

Three relay contacts indicate HC-DySC status. The contacts are form A and
close upon occurrence of the named event: (a) any SAG EVENT, when rms input
voltage drops below 88.5% of rated value; (b) OUTPUT OK, when output
voltage remains between 87% and 110%; and (c) a system ALARM event. The
relay contact ratings are 24V at 1A.

For access, remove the small metal cover from the top of the HC-DySC
(See

Figure 6

).

All wiring is to be Class 2, limited to 24 Volts, AC or DC.

Acceptable wire gauges range from 24AWG to 12AWG (0.205-2.5mm2).

Torque connections to 5.0 lb-in (0.6 N-m).

For permanent installation of communications conductors, a standard
conduit knockout is located on the cabinet top (See

Figure 2

).

Figure 6 - Access Cover Location