Specifications, Brake fuse – Rockwell Automation 1305 DYNAMIC BRAKES User Manual

Page 9

Advertising
background image

1305 Dynamic Brake

9

1305-5.11 May, 1999

Braking Torque

100% torque for 20 seconds (typical).

Duty Cycle

20% (maximum).

Temperature

0˚C to 50˚C (32˚F to 122˚F).

Humidity

0 to 95% non-condensing.

Atmosphere

Cannot be used in atmospheres having corrosive or
hazardous dust, vapor, or gas.

Altitude Derating

0 to 1,000 meters without derating.

Enclosure Type

IP20

Codes and Standards

UL, cUL.

Specifications

ATTENTION: Electric Shock can cause injury or death.
Remove all power before working on this product.

For all dynamic brake ratings, DC brake power is supplied
from the drive DC Bus.

Hazards of electrical shock exist if accidental contact is
made with parts carrying bus voltage. A bus charged
indicator on the drive provides visual indication that bus
voltage is present. Before proceeding with any installation
or troubleshooting activity, allow at least 60 seconds after
input power has been removed for the bus circuit to
discharge.

!

Brake Fuse

All dynamic brakes are internally fused to protect brake components.
When replacing the brake fuse, use only the type and size specified
below. Replace the brake if the fuse blows repeatedly.

Important:

Brakes are not repairable.

Dynamic Brake

Fuse

Type

Rating

KAA12

F1

Gould Shawmut A60Q15-2

15A, 230V

KBA03

F1

Gould Shawmut A60Q10-2

10A, 460V

KBA06

F1

Gould Shawmut A60Q10-2

10A, 460V

KBA09

F1

Gould Shawmut A60Q10-2

10A, 460V

Advertising