Maximum Module Current

·

10 Amps per relay output

·

Maximum continuous current for two adjacent relays is 12 Amps.

Le courant permanent maximum pour deux relais adjacents est de 12 A.
Der maximale Dauerstrom für zwei nebeneinanderliegende Relais beträgt 12 A.
La corrente continua massima per due relè adiacenti è di 12 ampere.
La corriente continua máxima para dos relés adyacentes es de 12 A.

Replacement Relays

·

24VDC Control (Coil) Voltage: 700-HK36Z24

·

120VAC Control (Coil) Voltage: 700-HK36A1

Relay Contact Rating
Spécification du Contact à Relais
Relaiskontakt-Nennwerte
Classificazione Contatti di Relay
Capacidad Nominal del Contacto de Relé

700-HK36 _ _

Electrical Ratings

120VAC

AC-15, 6.2 A
B300 Pilot Duty, 3 A
1/3 HP (0.24 kW) 1-Phase

240VAC

AC-15, 3.1 A
B300 Pilot Duty, 1.5 A
3/4 HP (0.55 kW) 1-Phase

230VAC

0.55 kW 1-Phase

24VDC

DC-13, 5.0 A

125VDC

DC-13, 0.2 A
R300 Pilot Duty, 0.22 A

250VDC

DC-13, 0.1 A
R300 Pilot Duty, 0.11 A

Contacts

Inductive VAC

Inductive VDC

230VAC

AC-1, 16 A

277VAC

Minimum Permissible Contact Ratings

300mW (5V / 60mA or 60V / 5mA) for Silver Contacts)

16 A General Use

30VDC

DC-1, 12 A
10 A, Resistive

Resistive

Make, Break and Continuous

10

5

10

6

10

7

0

4

8

700-HK36 SPDT

Electrical Life (AC Loads) versus Contact Life

700-HK36 SPDT Maximum DC1 Breaking Capacity

Electrical Life (DC Loads) versus Contact Life

12

16

(A)

Cycles

Resistive Load - cos = 1
Inductive Load - cos = 0.4

1

2

4

6

10

20

0.1

0.2

20

60

100

DC Voltage (V)

DC Breaking Current (A)

140

180

220

Rated Insulation Voltage (Ui)

250V IEC, 300V UL/CSA

1-Pole, 1 CO, SPDT - 16A

Rated Thermal Current (I

th

)

·

When switching a resistive load (DC1) having voltage

and current values under the curve, an electrical life
of > 100 x 10

3

can be expected.

·

In case of inductive loads (DC13), the connection of a

diode in parallel with the load will permit a similar
electrical life as for a DC1 load. Note: the release
time for the load will be increased.

Resistive Load