EN921 - Variable Voltage w/ PI Power/Current Control

Voltage Control

[Volt Incr Time]

This value determines the time it will take the drive to ramp
from 0 Volts to [Maximum Voltage] when [Control Select]
is set to “Variable Voltage”. The rate determined by this
value and [Maximum Voltage] is linear.

Parameter Number

334

Parameter Type

Read and Write

Display Units / Drive Units

0.1 Second / Seconds x 10

Factory Default

10.0 Sec

Minimum Value

0.0 Sec

Maximum Value

3600.0 Sec

[Volt Decr Time]

This value determines the time it will take the drive to ramp
from [Maximum Voltage] to 0 Volts when [Control Select]
is set to “Variable Voltage”. The rate determined by this
value and [Maximum Voltage] is linear.

Parameter Number

335

Parameter Type

Read and Write

Display Units / Drive Units

0.1 Second / Seconds x 10

Factory Default

10.0 Sec

Minimum Value

0.0 Sec

Maximum Value

3600.0 Sec

[Voltage Command]

This parameter displays the commanded voltage value
from the reference specified by [Volt Select].

Parameter Number

336

Parameter Type

Read Only

Display Units / Drive Units

1 Volt / 4096 = Drive Rated Volts

Factory Default

None

Minimum Value

0 Volts

Maximum Value

120% Rated Drive Output Voltage

[Volt Select]

This parameter specifies which input signal will be used
as the [Volt Command] reference when [Control Select] is
set to “Variable Voltage”.

Parameter Number

337

Parameter Type

Read and Write

Factory Default

“Volt Preset”

Units

Display Drive

“Analog In 0” 0
“Analog In 1” 1
“Analog In 2” 2

“Volt Preset” 3

Refer to [Volt Preset] Value

“Adapter 1-6” 4-9

“Volt Cmd Ref” 10 Refer to [Volt Command Ref] Value

“Voltage PI” 11 Refer to “Voltage PI” Group

[Volt Preset]

This parameter specifies the output voltage setpoint value
when [Volt Select] is set to “Volt Preset”.

Parameter Number(s)

338

Parameter Type

Read and Write

Display Units / Drive Units

1 Volt / 4096 = Drive Rated Volts

Factory Default

0 Volts

Minimum Value

0 Volts

Maximum Value

120% Drive Rated Volts

[Volt Trim Select]

This parameter specifies which input signal will be used to
trim (increase/decrease) the [Volt Command] reference.
Volt trim is only active when [Volt Trim%] is set to a non-zero
value.

Parameter Number

339

Parameter Type

Read and Write

Factory Default

“Analog In 1”

Units

Display Drive

“Analog In 0” 0
“Analog In 1” 1
“Analog In 2” 2

“Volt Preset” 3

Refer to [Volt Preset] Value

“Adapter 1-6” 4-9

“Volt Cmd Ref” 10 Refer to [Volt Command Ref] Value