EN921 - Variable Voltage w/ PI Power/Current Control

Voltage PI

[PI Feedback]

This parameter displays the current value of the reference
selected by [PI Fdbk Select].

Parameter Number

218

Parameter Type

Read Only

Display Units / Drive Units

None / 4096 = 100%

Factory Default

None

Minimum Value

–4915

Maximum Value

4915

[PI Error]

The value of the error calculated by the PI loop. This value
is the difference between [PI Reference] & [PI Feedback]
and determines the PI output.

Parameter Number

219

Parameter Type

Read Only

Display Units / Drive Units

None / 4096 = 100%

Factory Default

None

Minimum Value

–4915

Maximum Value

4915

[PI Output]

The current output of the PI loop is displayed with this
parameter. This output is used as the reference for the
voltage output.

Parameter Number

220

Parameter Type

Read Only

Display Units / Drive Units

1 Volt / 4096 = Drive Rated Volts

Factory Default

None

Minimum Value

–120% Rated Voltage

Maximum Value

120% Rated Voltage

[KI Process]

This parameter sets the integral gain of the process PI
loop.

Parameter Number

221

Parameter Type

Read/Write

Display Units / Drive Units

NA / NA

Factory Default

128

Minimum Value

0

Maximum Value

2048

[KP Process]

This parameter sets the proportional gain of the process
PI loop.

Parameter Number

222

Parameter Type

Read/Write

Display Units / Drive Units

NA / NA

Factory Default

256

Minimum Value

0

Maximum Value

2048

[PI Neg Limit]

This parameter sets the lower (negative) limit of the PI
output.

Parameter Number

223

Parameter Type

Read/Write

Display Units / Drive Units

None / 4096 = 100%

Factory Default

-341

Minimum Value

–4915

Maximum Value

4915

[PI Pos Limit]

This parameter sets the upper (positive) limit of the PI
output.

Parameter Number

224

Parameter Type

Read/Write

Display Units / Drive Units

None / 4096 = 100%

Factory Default

341

Minimum Value

–4915

Maximum Value

4915

[PI Preload]

Sets the value used to preload the PI integrator when “Set
Output” or “Preload Int” bits equal “1” in [PI Config].

Parameter Number

225

Parameter Type

Read/Write

Display Units / Drive Units

None / 4096 = 100%

Factory Default

0

Minimum Value

–4915

Maximum Value

4915