Rockwell Automation 1606-XLS80E DC Power Supply User Manual

Page 3

Advertising
background image

1606-XLS80E Power Supply Instruction Manual

Technical Data

1606-XLS80E

Output Voltage

DC 24-28V

externally adjustable

Factory Set

typ.

24.1V

at full rated load

Output Current

min

3.4-3.0A

continuous

min

5.0-4.5A

for typ. 4 sec

Output Power

min.

80W

continuous

min.

120W

for typ. 4 sec

Output Ripple

max. 50mVpp

BW DC to 20MHz

Over-voltage Protection

max. 36Vdc

AC Input Voltage

-

AC 100-240V

-15/+15%

, 50-60Hz

TN, TT and IT mains

AC Input Current

max. 1.8-1.0A

at 100 - 240Vac

DC Input

-

DC 110-300V -20/+25%

DC Input Current

max. 0.85-0.3A

at 110 - 300Vdc

Power Factor

typ.

0.55-0.47

at 100 - 230Vac

AC Inrush Current

max. 6A peak, 2A

2

s

at 100Vac

max. 7A peak, 2A

2

s

at 120Vac

max. 13A peak, 2A

2

s

at 230Vac

Efficiency

typ.

88.7 / 90.0%

at 120 / 230Vac

Losses

typ.

10.4 / 9.1W

at 120 / 230Vac

Hold-up Time

typ.

21ms

at 100Vac

typ.

35ms

at 120Vac

typ.

167ms

at 230Vac

Capacitive Loads

-

No limitations

Inductive Loads

-

No limitations

Limited Warranty

-

1 year

Environment

Protection

Operational temperature

-25 to +70°C

De-rate above +60°C

Output

Overload, no-load, short-circuit proof

Storage temperature

-40 to +85° C

Storage, transport

Degree of protection

IP 20

EN/IEC 60529

Humidity

5 to 95% RH

No condensation allowed

Class of protection

I

PE (Ground) connection required!

Vibration sinusoidal

2g

IEC 60068-2-6

Degree of pollution

2

EN 50178, not conductive

Shock

15g 6ms, 10g 11ms

IEC 60068-2-27

Over-temperature protection

yes

Output shut-down with automatic restart

Output over-voltage protection

yes

Output shut-down with automatic restart

Over-voltage category

III

EN 50178

Penetration protection

>3.5mm

e.g. screws, small parts …

Internal input fuse

T6.3A

Device protection, not externally
accessible

Allowed output current versus
the ambient temperature

Ambient temperature is defined
2cm below the unit.

0%

25%

50%

75%

100%

125%

150%

-40°C -20°C

0°C

20°C 40°C

60°C 80°C

Ambient Temperature

for ty p. 4s

continuous

External protection

The unit is tested and approved for branch circuits
up to 20A. External protection is only required, if the
supplying branch has an ampacity greater than this.
The minimum rating of an external circuit breaker or
fuse shall be 6A (B-characteristic) or 6A (C-
characteristic) to avoid a wrong tripping of the fuse.

Functional Diagram

Dielectric Strength

Type tests and factory tests:
Conducted by the manufacturer.
Do not repeat test in field!
Field test rules:

(1) Use appropriate test equipment which
apply the voltage with a slow ramp!
(2) Connect L and N together as well as all
output poles.
(3) Use only AC test-voltages with 50/60Hz.
The output voltage is floating and has no ohmic
reference to ground.

A

C

N

L

Input

Earth

Output

-

+

B

A

B

C

Type Test

60s

2500Vac

3000Vac

500Vac

Factory Test

5s

2500Vac

2500Vac

500Vac

+

+

-
-

V

OUT

Input Fuse
Input Filter
Input Rectifier
Inrush Limiter
Transient Filter

Output

Voltage

Regulator

Power

Converter

Output

Filter

Output

Voltage
Monitor

Output

Power

Manager

Temper-

ature

Shut-

down

Over-

load

DC

ok

Output

Over-

Voltage

Protection

L

N

Field Test

5s

2000Vac

2000Vac

500Vac

Overload Performance

The unit is designed to support loads with a higher short-
term power requirement without damage or shutdown.

Repetitive pulse loading:

Multiple pulses can be supported as long as the average
(R.M.S.) output current stays below the specified continuous
output current. If it is higher, the unit will respond with a
thermal shut-down.

Examples for pulse load
compatibility:

P

PEAK

P

0

T

PEAK

T

0

120W

80W

1s

>25s

120W

0W

1s

>1.3s

120W

40W

0.1s

>0.16s

120W

40W

1s

>1.6s

0V

4V

8V

12V

16V

20V

24V

28V

0A

1A

2A

3A

4A

5A

6A

0s

1s

2s

3s

4s

5s

6s

7s

8s

110% 120% 130% 140% 150% 160%

120W

40W

3s

>4.9s

Output characteristic (typ.)
Curve is valid for the 24V unit. Units with
output voltages other than 24V have an
equivalent and proportional performance.

Bonus time
Duration until the output starts dipping.
Bonus Time is hardware controlled.
min. / typ. / max.

t

100%

P

PEAK

0%

T

PEAK

P

0

T

0

P

OUT

max.

150%

t

continuous

Short

term