1606-XLS80E Power Supply Instruction Manual


Safety

Separation of output

SELV

IEC/EN 60950-1

EMC

The device is suitable for applications in industrial environment as well as in residential,
commercial and light industry environment without any restrictions.
For further details see datasheet.

PELV

EN 60204-1, EN 50178, IEC 60364-4-41

EMC Immunity

EN 61000-6-1, EN 61000-6-2

Touch current

max. 0.3 mA

Earth leakages current, TN- mains

Isolation resistance

min. 5MOhm

Input to output, 500Vdc

EMC Emission

EN 61000-3-2, EN 61000-3-3, EN 61000-6-3, EN 61000-6-4,
FCC Part 15 Class B

PE resistance

max. 0.1Ohm

Between housing and ground terminal

Transformer

Safety transformer according to IEC/EN 61558-2-17

This device complies with FCC Part 15 rules. Operation is subjected to following two
conditions: (1) this device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that may cause undesired operation.

Approvals

See datasheet or markings on the unit

CE mark in conformance with EMC guideline 89/336/EEC and 93/68/EEC and low-voltage directive (LVD) 73/23/EWG.


Terminals and Connections

Terminals

Input

Output

Type

Bi-stable, quick-connect spring clamp terminals

Ferrules

Allowed, but not required

Solid wire

0.5-6mm

2

0.3-4mm

2

Stranded wire

0.5-4mm

2

0.3-2.5mm

2

AWG

AWG 20-10

AWG 28-12

Stripping length

10mm / 0.4inch

6mm / 0.25inch

Pull-out force

10AWG:80N, 12AWG:60N, 14AWG:50N, 16AWG:40N (UL486E)

1. Insert the wire

2. Snap the lever

Use appropriate copper cables that are designed for an operating temperatures of 60°C (for ambient
up to 45°C) and 75°C (for ambient up to 60°C), minimum. Follow national installation codes and
regulations! Ensure that all strands of a stranded wire enter the terminal connection! Up to two
stranded wires with the same cross section are permitted in one connection point (except PE wire). Do
not use without PE (Ground) connection!


Physical Dimensions, Indicators and Cooling

Width

32mm / 1.26’’

Height

124mm / 4.88’’

Depth

102mm / 4.02’’

Plus DIN-rail depth

Weight

420g / 0.93lb

DIN-Rail

Use DIN-rails according to EN 60715 or EN 50022
with a height of 7.5 or 15mm

Mounting
Orientation

Output terminal on top and input terminals on the bottom.
For other orientations consult factory.

Indicators

DC-ok LED
(green)

Overload
lamp (red)

Normal operating mode

ON

OFF

BonusPower

®

operation

ON

OFF

Overload (V

OUT

< 90%)

ON

ON

Overload (V

OUT

< 80%)

OFF

ON

Short-circuit (V

OUT

= 0)

OFF

ON

Temperature shut-down

Flashing

Flashing

No input power

OFF

OFF

Do not obstruct air flow! The unit is convection cooled. Ventilation grid must be kept free of any obstructions.
Keep installation clearances at higher ambient temperature and full load:
60mm on top and on the bottom, 15mm on the left and right side

PU-358.010.38-10A

Operation on Two Phases

240V max.

Fuse

DC

L

N

PE

N

L2

Center

Tap

L1

L3


(1) The rated supply voltage must be below
240V.

(2) Use an appropriate fuse to protect the N
terminal!

Parallel Operation

Power Supply A

Power Supply B

-

AC

DC

+

-

AC

DC

+

Load

+

-

Fuse

*)

Fuse

*)

(1) Power supplies can be paralleled to
increase output power or to build redundant
systems.
(2) For parallel operation use power supplies
of the same family.
(3) Use load connection wires of the same
gauge and length.
(4) Set the output voltages of all power
supplies to the same value.
(5) A fuse is only required if more than three
units are connected in parallel.

Serial Operation

Load

Power Supply A

Power Supply B

+

-

AC

DC

+

-

AC

DC

+

-

Earth

*)


(1) It is possible to connect as many units in
series as needed, providing the sum of the
voltage does not exceed 150Vdc.
(2) For serial operation use power supplies
of the same type.
(3) Grounding of the output is required when
the sum of the output voltage exceeds
60Vdc.

Operation with DC Input

Fuse

+

-

Load

+

-

DC

L

N

PE

AC

+

-


(1) The power supply will operate with a DC
input voltage.
(2) Use a battery or similar DC source.
(3) Connect +pole to L and –pole to N
(4) In case the –pole of the battery is not
grounded, use an appropriate fuse to protect
the N terminal.
(5) Connect the ground terminal of the power
supply to a PE wire or to machine ground.

Check touch current (earth leakage current)! The total touch current is the sum of
the touch currents of all units. Safety limits – depending on the field of application
- apply for the allowed touch current!

Air flow

open

close