Standby mode, Charging mode – Rockwell Automation 1606-XLSBUFFER24 Power Supply Reference Manual User Manual

Page 4

Advertising
background image

All parameters are specified at 24V, 20A, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

4

Rockwell Automation Publication 1606-RM026A-EN-P — April 2014

Bulletin 1606 Switched Mode Power Supplies

5. Standby Mode

Input voltage

nom. DC

24V

Voltage range

nom. 24-28.8Vdc

Input current

typ. 80mA

Standby

mode

Power dissipation

typ. 1.9W

Status lamp

always on

Active signal

high ohmic

Ready signal

low ohmic

6. Charging Mode

Charging current

min. 0.4A

Charging

mode

max. 0.6A

Charging

mode

Charging time

min.

20s / 15s

Initial charge

1)

/ Re-charging

2)

max.

29s / 21s

Initial charge

1)

/ Re-charging

2)

Status lamp

flashes 1.25Hz

Active signal

high ohmic

Ready signal

high ohmic

1) Initial charging is the first charge after voltage is applied to the buffer unit.
2) Re-charging is the charging of the internal capacitors after voltage interruptions of less than 2 minutes.

Fig. 6-1 Re-charging time, 24V

Charge

20

0

5

10

30s

Charging Time

40

80

60

100%

15

20

25

max

min

Advertising