Buffer mode – Rockwell Automation 1606-XLSBUFFER24 Power Supply Reference Manual User Manual

Page 5

Advertising
background image

All parameters are specified at 24V, 20A, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM026A-EN-P — April 2014

5

Bulletin 1606 Switched Mode Power Supplies

7. Buffer Mode

Rated output current

nom.

20A

Current limitation

min.

20A

Electronically limited

Output voltage

typ.

22.5V

Jumper in position “22.5V fixed”

typ.

1V below input
voltage

Jumper in position “Vin –1V”

Ripple and noise voltage

max.

200mVpp

20Hz to 20MHz, 50Ohm

Hold-up time

min.

0.2s

22.5V, 20A

typ. 0.31s

22.5V,

20A

min. 28s

22.5V,

0.1A

typ. 43s

22.5V,

0.1A

To increase buffer current or extend hold-up time, any given number of buffer
units can be installed in parallel.

Activation threshold

typ.

22.5V

Ju

mper in position “22.5V fixed”

Buffering starts if terminal voltage falls below 22.5V.

typ.

Vin –1V

Jumper in position “Vin –1V”
Buffering starts if the terminal voltage decreases by
more than 1V. Buffering ends when terminal voltage
increases by more than 1V
Voltage changes slower than 0.54V/s will be ignored
unless the voltage is above 22.5V. Below 22.5V
buffering starts immediately.

Status lamp

flashes 10Hz

Active signal

low ohmic

Ready signal

high ohmic


Fig. 7-1 Hold-up time

0,1 A

1,0 A

10,0 A

100,0 A

0,1 s

1,0 s

10,0 s

100,0 s

Buffer

Current

typ. ( 22,5 V )

typ. ( 27,8 V )

min. ( 22,5 V )