Chapter 6 - using messages, Using messages, Chapter 6 – Rockwell Automation 1203-CN1 ControlNet Communications Module 1203-CN1 User Manual

Page 67: Chapter

Advertising
background image

Publication 1203-5.13 – February, 2002

Chapter

6

Using Messages

Chapter Objectives

Chapter 6 provides information about using messages on the
ControlNet network. It includes the following:

Required equipment and software.

Discussion of messaging.

Examples of rungs that enable messaging.

This chapter assumes you already have experience creating ladder
logic programs and using messages in RSLogix5.

Required Equipment and Software

Before adding messages to a PLC ladder logic program, your PC
should be:

Running RSLogix5 and RSLinx applications. Refer to
http://www.software.rockwell.com for more information on these
products.

Connected to and communicating with the ControlNet network
using a 1784-KTCX card, 1784-PCC card or 1770-KFC adapter.

Using Messages

Messaging lets you view and modify SCANport product parameters
as well as provides access to other internal SCANport-related
information and services.

To use messaging, you need to:

1. Insert a MSG rung in your ladder logic program. A unique

message number must be used for each message.

2. Insert a control word in the MSG rung.

3. Configure the message using the MSG dialog box.

The following must be completed in the This PLC-5 section:

In the Communication Command field, use the drop-down
list to specify whether the MSG instruction performs a read
or write operation and what type of message is used.

In the Data Table Address field, enter the data table address
containing the message in the controller (e.g., PLC-5).

In the Size in Elements field, enter the number of elements
being transferred.

In the Port Number field, enter 2 to enable the ControlNet
dialog parameters.

Advertising