Hold-up time – Rockwell Automation 1606-XLP15E Power Supply Reference Manual User Manual

Page 7

Advertising
background image

All parameters are specified at 24V, 0.63A, 230Vac input, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM004A-EN-P - January 2014

7

Bulletin 1606 Switched Mode Power Supplies

7. Hold-up Time

AC 100V

AC 120V

AC 230V

Hold-up Time

typ.

64ms

98ms

375ms

at 24V, 0.32A, see Fig. 7-1

typ.

31ms

47ms

196ms

at 24V, 0.63A, see Fig. 7-1

Note: At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is also on during this time


Fig. 7-1 Hold-up time vs. input voltage

Fig. 7-2 Shut-down behavior, definitions

0

25

50

125

150ms

85

120

155

190

230Vac

Input Voltage

Hold-up Time

75

100

a) 24V 0.32A typ.

b) 24V 0.32Amin.

c) 24V 0.63A typ.

d) 24V 0.63A min.

a

b

c

d

- 5%

Hold-up Time

Zero Transition

Output
Voltage

Input