1397 300HP AC Line Disconnect

5

1397-5.27 October, 1997

TORQUE

14-10GA 35 LB.-IN.

0 GA 48 LB.-IN.

SPEC

GND

!

DANGER

RISK OF ELECTRICAL SHOCK. DISCONNECT INPUT
POWER BEFORE SERVICING EQUIPMENT.

P/N 33145

DANGER

CIRCUIT BREAKER DOES NOT DISCONNECT INCOMING A0
LINE POWER IT ONLY PROVIDES DC FAULT PROTECTION.

LE DISCONECTEUR NE COUPTE PAS L'AUTOMENTATION DU SPOTEUR IL NES
SERT QUE A ASSURER UNE PROTECTION CONTRE LES DESFAULTS DC.

810903-2424

283

282

281

4FU 5FU 6FU 7FU 8FU

183

182

181

RISK OF SHOCK

REPLACE AFTER

SERVICING

DANGER

!

Plastic

Line Fuse

Cover

81

82

83

ON

OFF

Line Side

Label

M12 Nut

and Washer

Removed

Previously

M12 Nut

and Washer

Removed

Previously

M12 Nut

and Washer

Removed

Previously

7/16"
Flat Washer
7/16" Split
Lockwasher
7/16" x 1" Bolt
— (6) Places —

7a

Remove the disconnect’s bottom lug cover by loosening the (2)
screws holding it in place. Put one split lockwasher and one flat
washer onto each of the bolts used to fasten the bus bars to the
disconnect.

DS300 Installation

7b

Attach one bus bar to the

drive’s left line fuse connector
and the disconnect’s left load
connector. One of the holes on
the bus bar attaches to the lug
for the line fuse connector. Use
(2) of the bolt, lockwasher and
flat washer 7/16" assemblies

7c

Fasten the bus bars to the

drive’s line fuse connectors
with the M12 nuts and
washers removed in

Step 1

.

• Tighten the bolts fastening

the bus bars to the
disconnect to 40N-m
(350lb.-in.).

• Tighten the nuts fastening

the bus bars to the line fuse
connectors to 40N-m
(350lb.-in.).

to attach the bus

bar to the

disconnect.

Repeat this
procedure to
attach the
remaining

bus bars.