Hardwiring – Rockwell Automation 1609-P10000E Quick Start Guide for 8000 / 10000 VA Uninterruptible Power Supply User Manual

Page 3

Advertising
background image

2

Hardwiring

Wiring must be performed by a qualified electrician.

1. Install a utility circuit breaker in accordance with local electrical codes (see tables below) for input wiring only.
2. Switch the UPS input circuit breaker and utility circuit breakers OFF.
3. Remove the access panel.
4. Remove circular knockouts.
5. Run wires through access panel to terminal blocks. Wire to ground block first. Adhere to all national and local electrical

codes.

6. Use appropriate glands to achieve strain-relief on the hardwired input and output power cables.

Input Connection

Output Connection (optional)

Wire to L1, L2,

Wire to L1A, L2A,

System Wiring

Voltage

Current
Full Load
(Nominal)

External Input
Circuit Breaker
(typical)

Wire Size
(typical)

1609-P8000E

Input & Output

208/230 V

40 A
220 V 38 A

50 A / 2-pole for
Input Wiring Only
Rockwell part #
1492-MCAA2H50

# 8 AWG
10mm

2

1609-P10000E

Input & Output

208/230 V

54 A
220 V 50 A

70 A / 2-pole for
Input Wiring only
Rockwell part #
1492-MCBA2H70

# 6 AWG
16mm

2

7. Switch the circuit breakers ON.
8. Check line voltages.
9. Replace the access panel.