Rockwell Automation 1609-P10000E Quick Start Guide for 8000 / 10000 VA Uninterruptible Power Supply User Manual

Page 7

Advertising
background image

6

U

SER

C

ONFIGURABLE

I

TEMS

N

OTE

:

S

ETTINGS ARE MADE THROUGH SUPPLIED

P

OWER

C

HUTE SOFTWARE

,

OPTIONAL

N

ETWORK

M

ANAGEMENT CARDS

,

OR

T

ERMINAL

M

ODE

.

F

UNCTION

F

ACTORY

D

EFAULT

U

SER

S

ELECTABLE

C

HOICES

D

ESCRIPTION

Automatic Self-Test

Every 14 days
(336 hours)

Every 7 days
(168 hours),
Every 14 days
(336 hours),
On Startup Only,
No Self-Test

Set the interval at which the UPS will execute
a self-test.

UPS ID

UPS_IDEN

Up to eight characters to
define the UPS

Uniquely identify the UPS, (i.e. server name
or location) for network management
purposes.

Date of Last Battery Replacement

Manufacture Date

mm/dd/yy

Reset this date when you replace the battery
modules.

Minimum Capacity Before Return
from Shutdown

0 percent

0, 15, 25, 35, 50, 60, 75,
90 percent

Specify the percentage to which batteries will
be charged following a low-battery shutdown
before powering connected equipment.

Alarm Delay After
Line Failure

5 second delay

5 second delay,
30 second delay,
At Low Battery,
Never

Mute ongoing alarms or disable all alarms
permanently.

Shutdown Delay

20 seconds

0, 20, 60, 120, 240, 480,
720, 960 seconds

Set the interval between the time when the
UPS receives a shutdown command and the
actual shutdown.

Duration of
Low Battery Warning.

2 minutes
PowerChute
software provides
automatic,
unattended
shutdown when
approximately two
minutes of battery
runtime remains.

2, 5, 7, 10, 12, 15, 18,
20 minutes.

The low battery warning beeps become
continuous when two minutes of runtime
remains.
Change the warning interval to a higher setting
if the operating system requires a longer
interval for shutdown.

Synchronized Turn-on Delay

0 seconds

0, 20, 60, 120, 240, 480,
720, 960 seconds

Specify the time the UPS will wait after the
return of utility power before turn-on (to avoid
branch circuit overloads).

High Bypass Point

+10% of
output voltage
setting

+5%, +10%, +15%,
+20%

Maximum voltage that the UPS will pass to
connected equipment during internal bypass
operation.

Low Bypass Point

-30% of output
voltage setting

-15%, -20%, -25%, -30% Minimum voltage that the UPS will pass to

connected equipment during internal bypass
operation.

Output Voltage

208/230 V models:
230 VAC

208/230 V models:
200, 208, 220,
230, 240 VAC

Allows the user to select the UPS output
voltage while online.

Output Frequency

Automatic
50 ± 3 Hz or
60 ± 3 Hz

50 ± 3 Hz,
50 ± 0.1 Hz
60 ± 3 Hz
60 ± 0.1 Hz

Sets the allowable UPS output frequency.
Whenever possible, the output frequency
tracks the input frequency.

Number of Battery Packs

1

Number of Connected
Batteries (four battery
modules per pack)

Defines the number of connected battery packs
for proper runtime prediction.